Online Tools
常用电子 / 电工 / 传感器 / Thermal Design / Mechanics / Thermodynamics / 电磁学Calculate工具
198电子 / 电工 / 嵌入式 / 传感器 / Thermal Design / Mechanics / Thermodynamics / 电磁学High频Calculate器,SVG 图示Calculate模型,填参数即时出结果:Resistance分压、DC-DC 反馈Resistance、TL431 反馈(Flyback / Forward)、PCB 阻抗 / 载流、CAN bits定时、CRC check、4-20mA、NTC / PT100、PLC 模拟量、散热器选型、Battery stringandCharge、Sallen-Key 滤波器、传输线延时、VSWR、motor选型、线路voltage drop、calorie诺效率……
Resistor Voltage Divider
上臂 R1 接Input、下臂 R2 接地:既可按给定 R1/R2 算Output voltage,也可由Input量程and ADC 参数枚举StdResistance,给出Source impedance合适的采样最佳组合。
Vout = Vin × R2 / (R1 + R2) | ADC: R2/(R1+R2) = Vref(1−Margin)/Vin,maxused 84 timesSeries / Parallel Resistance
Equivalent resistance of series or parallel resistors, with k / M suffixes (e.g. 4.7k, 1M), up to 8 values.
series Rs = ΣRi | parallel 1/Rp = Σ(1/Ri)used 5 timesParallel Capacitor Calculator
Equivalent capacitance, total charge, and stored energy for parallel capacitors; supports pF / nF / µF / mF / F suffixes, up to 12 capacitors.
C_p = ΣCi | Q = C_p·V | E = ½·C_p·V²Wheatstone Bridge Calculator
Wheatstone bridge balance / output: solve the unknown arm from three resistors, or compute offset voltage, Thevenin resistance, and sensitivity from all four arms.
R1·Rx = R2·R3 | Vout = Vex·[R3/(R1+R3) − Rx/(R2+Rx)] | Rth = R1∥R3 + R2∥Rxused 1 timesCapacitor Charge / Discharge Energy Calculator
Energy accounting for capacitor charge / discharge: source output, capacitor energy change, resistor / loop loss, charging efficiency, and average power at a repetition rate.
ΔQ = C·(V1−V0) | ΔE = ½C(V1²−V0²) | charge E_source = Vs·ΔQ | E_loss = E_source − ΔEused 2 timesResistor Color Code
Read resistance and tolerance from 4- or 5-band codes; the bands render live in the diagram.
R = (significant digits) × multiplier | 5-band adds one digitRC Filter / Cutoff Frequency
First order RC Low通 / High通滤波Calculate:由 R、C 求Cutoff frequency fc and任意频点衰减,或由 fc 反推 R / C,或按 fc 推荐标准 R、C 组合。
fc = 1 / (2πRC) | τ = RC | R = 1/(2π·fc·C) | C = 1/(2π·fc·R)used 6 timesLC Resonance Frequency
LC 回路的谐振Frequencyand特性阻抗:由 L、C 求 f0,或由 f0 反推 L / C,或按 f0 推荐标准 L、C 组合,用于选频网络、Antenna匹配andsupply滤波。
f0 = 1 / (2π√(LC)) | Z0 = √(L/C) | L = 1/((2π·f0)²·C) | C = 1/((2π·f0)²·L)SMD Resistor Marking Calculator
Convert SMD resistor markings and resistance in both directions: 3-digit code (103 = 10 kΩ), 4-digit code (1002 = 10 kΩ), R decimal notation (4R7 = 4.7 Ω, R47 = 0.47 Ω) and EIA-96 precision code (01C = 10 kΩ), including all-zero jumpers.
3-digit AB×10^C | 4-digit ABC×10^D | R as decimal point | EIA-96: index (01–96) × multiplier letterused 25 timesSMD Capacitor Code (104 = 100nF)
Two-way conversion between three- and four-digit EIA capacitor codes and capacitance, with code cross-reference, unit conversion and tolerance letters.
Code ABc = AB × 10^c pF (104 → 10×10⁴ = 100nF)used 7 timesSMD Inductor Code (101 = 100µH)
Two-way conversion between three-digit inductor codes and inductance in µH, including the R decimal notation.
Code ABc = AB × 10^c µH (101 → 10×10¹ = 100µH)E-Series Value Picker (E24 / E96 / E192)
Given a target resistance, find the nearest E24/E96/E192 value and search series/parallel pairs that approach it — turn an odd value into something you can actually buy.
E96 has 96 steps per decade, adjacent ratio 10^(1/96) ≈ 1.0237used 15 timesResistor Color Bands (Value → Bands)
Given a value and tolerance, get the four- or five-band colour sequence with a drawn resistor — the fastest way to pick a part by eye.
4-band: digit · digit · multiplier · tolerance | 5-band: digit · digit · digit · multiplier · toleranceDC-DC Feedback Resistor Selection
From Vref and target output voltage, enumerate the best divider across E3–E192 series and report actual error.
Vout = Vref × (1 + R1/R2)used 27 timesLED Current-Limiting Resistor
Current-limiting resistor, dissipation, and recommended package power from supply, LED forward voltage, and current.
R = (Vin − Vf) / IfOhm’s Law / Power
From any two quantities (U/I/R/P), solve the other two — the universal starting point for circuit checks.
U = IR | P = UI = I²R = U²/RLDO Dropout Dissipation / Junction Temperature
Linear regulator dissipation, junction temperature, and efficiency — check thermals before selecting parts when dropout is large.
P = (Vin − Vout) × Iout | Tj = Ta + P × θJAused 2 timesBattery Life Estimate
Estimate runtime from capacity, average current, and usable depth of discharge, plus battery energy in Wh.
runtime = capacity × usable ratio / average currentused 2 timesSense-Resistor Current Measurement
Voltage drop, amplified output, and dissipation of a low-side sense resistor, with an ADC range check.
Vsh = I × Rsh | Vout = Vsh × Gused 8 timesPower Supply Sizing (Load Profile)
Determine rated supply tier, input power, and buffer capacitor from steady/peak current and load profile (resistive / capacitive / inductive / pulse).
P = max(U·I_pk, U·I_load·(1+margin)) | I_in = P/(η·U_in·cosφ) | C ≥ ΔI·t_pk/ΔVLi-ion Charge Time & C-Rate Calculator
From capacity and charge current, compute the C-rate plus theoretical and practical (efficiency-included) charge time, with the currents for 0.5C and 1C.
t ≈ ΔSOC · capacity / charge current / efficiencyBattery Pack Series/Parallel Calculator
From cell parameters and the S/P arrangement, compute pack voltage, capacity, energy, internal resistance and maximum continuous current — the 13S4P and 4S2P view at a glance.
V = S·Vcell | Ah = P·Ahcell | R = S·Rcell/P | Wh = V·AhUSB PD Power & Type-C Current Tier
Compute PD power, identify the Type-C current tier, check whether an E-Marker cable is mandatory, and get wire-gauge advice from current density.
P = V × I | above 3A an E-Marked cable is requiredTL431 Shunt Regulator / Output Setting
The most common TL431 circuit: R1/R2 divider sets the output (optimal combination enumerated across E3–E192), plus the series resistor Rs, resistor and TL431 dissipation, and cathode-current checks.
Vout = Vref × (1 + R1/R2) | Rs = (Vin − Vout)/(Iload + Ika_min + I_sense)TL431 + optocoupler Flybackfeedback calculation
Typical secondary-side TL431+optocoupler feedback for flyback: enumerate the divider from standard series, compute the LED limiting resistor, and derive the required primary current with CTR margin checks.
Vout = Vref × (1 + Ru/Rl) | R_led = (Vled − Vf − Vka)/If | If_min = Ic / CTR_minused 6 timesTL431 + optocoupler Forwardfeedback calculation
Typical secondary-side TL431+optocoupler feedback for forward: divider, LED limiting resistor, primary-side current derivation and margin checks (tap after the output LC filter; see notes for compensation).
Vout = Vref × (1 + Ru/Rl) | R_led = (Vled − Vf − Vka)/If | If_min = Ic / CTR_minused 1 timesPCB Trace Current Capacity
Safe current from width, copper weight, and allowed temperature rise per IPC-2221, plus trace resistance / drop.
I = k · ΔT^0.44 · A^0.725 (A in mil²)used 65 timesPCB Trace Width for Current
Work backwards per IPC-2221: from current and allowed rise, find minimum width rounded to 0.1mm.
A = (I/k)^(1/0.725) | W = A / Tused 38 timesPCB Characteristic Impedance
Quick characteristic impedance for microstrip / symmetric stripline (IPC-2141); check before routing USB, Ethernet, or RF traces.
microstrip Z0 = 87/√(εr+1.41) · ln[5.98h/(0.8w+t)]used 5 timesPCB Trace Resistance
DC resistance, drop, and dissipation from length, width, and copper weight — essential for long supply / sense traces.
R = ρ · L / (W · T), ρcopper = 1.724e-8 Ω·mused 69 timesVia current / resistance
Via resistance and current capacity from drill, board thickness, and plating — check before switching layers at high current.
R = ρ·L/A | A = π/4·[(d+2t)² − d²]used 10 timesPCB Differential Pair Impedance
Edge-coupled differential impedance from width, spacing, and dielectric thickness; compare to 90/100/120Ω targets with tuning hints.
Zdiff = 2·Z0·(1 − k·e^(−c·s/h))|microstrip k=0.48 c=0.96, stripline k=0.34 c=2.9used 63 timesPCB Spiral Inductor Designer
Planar spiral coil: inductance, DC resistance, rough Q, self-resonance, and current from turns, width, spacing, and outer diameter.
L = K1·µ0·n²·d_avg/(1+K2·ρ)|d_in = d_out − 2n·w − (2n−1)·sused 24 timesPCB Planar Transformer Designer
Planar transformer design: turns from the volt-second equation, rounded ratio, flux check, winding width/layers, and copper loss.
N1 ≥ Vin·D/(k_vs·f·B·Ae)|n = N2/N1 = Vout/(k_v·Vin·D)used 16 timesNFC PCB Antenna Design
13.56MHz PCB NFC antenna: square spiral inductance, resonance tuning capacitor (E6), Q and damping resistor, and read-range estimate.
L modified Wheeler|C = 1/((2πf)²·L) − Cp|H(d) = n·I·a²/(2(a²+d²)^1.5)used 41 timesWiFi/BT PCB Antenna Design
2.4GHz PCB antenna: λ/4 inverted-F (IFA) arm length or half-wave patch W/L/feed inset, with 50Ω feed width and clearance notes.
λ/4 arm = c/(4f·√εeff)|patch W = c/(2f)·√(2/(εr+1)), L = c/(2f·√εeff) − 2ΔLused 15 timesSMT Copper Shim (Current Shunt) Calculator
A high-current trace can be reinforced by a copper shim soldered onto the PCB: from the shim size, parallel copper foil and solder-joint resistance it computes equivalent resistance, shim/copper current sharing, ampacity, voltage drop, losses and temperature rise — or back-solves the minimum shim thickness for a given current.
R = ρ(T)·L/(W·t) | R_eq = R_shim ∥ R_pcb | I = √(h·A_surf·ΔT/(R_eq + R_solder))used 1 times555 Timer Frequency
Frequency / pulse width / duty for astable (square-wave) and monostable (fixed pulse) configurations.
astable f = 1.44/[(R1+2R2)C] | monostable T = 1.1·R·Cused 2 timesADC Code ↔ Voltage
Convert between ADC raw code and voltage, with 1 LSB resolution — handy for sensor calibration and serial raw data.
V = code / 2ⁿ × Vref | 1 LSB = Vref / 2ⁿused 6 timesPWM Resolution / Counts
Achievable bits and duty step from timer clock and PWM frequency, or verify a target resolution.
counts = Fclk / Fpwm | bits = log₂(counts)UART Baud Rate Divider
Baud divider and actual error from the peripheral clock (16× / 8× oversampling); large error means unreliable comms.
div = Fclk / (OS × baud) | error ≤ ±2% recommendedRise Time ↔ Bandwidth Calculator
Derive the equivalent signal bandwidth from edge rise time, or the edge from the bandwidth — for scope selection, sample rate and impedance-control decisions.
BW = 0.35 / t_r (Gaussian response)Transmission Line Delay & Length Matching
From the effective dielectric constant, get propagation delay per millimetre, the λ/4 length, the critical trace length that needs termination and how much length a skew budget allows.
t_pd = 3.336·√εeff ps/mm | l_crit = t_r/2 ÷ t_pdADC ENOB / SNR / Oversampling
Derive ENOB from measured SNR and see how many bits oversampling buys back — for when a "12-bit" ADC behaves like 10 bits.
SNR_ideal = 6.02·N + 1.76 dB | ENOB = (SNR − 1.76)/6.02 | 4× oversampling ≈ +1 bitSallen-Key Low-Pass Filter Designer
Single op-amp second-order Sallen-Key low-pass: given cutoff and Q, get standard R/C values, the real fc/Q, peaking and a Bode plot.
f_c = 1/(2πR√(C1·C2)) | Q = ½·√(C1/C2) with R1 = R2 = Rused 78 timesSallen-Key High-Pass Filter Designer
Single op-amp second-order Sallen-Key high-pass: given cutoff and Q, derive standard C/R values, verify the real parameters and plot the response.
f_c = 1/(2πC√(R1·R2)) | Q = ½·√(R2/R1) with C1 = C2 = Cused 72 timesRC High-Pass Filter Calculator
First-order passive RC high-pass: get the cut-off from R/C or back out the components from a target f_c, with attenuation and phase at a probe frequency.
f_c = 1/(2πRC) | |H| = (f/f_c)/√(1+(f/f_c)²)Op-Amp Bandwidth & Slew Rate Check
Check whether an op-amp can sustain the target frequency and amplitude under both GBW and slew-rate limits, and get the usable upper frequency.
f_cl = GBW/A_cl | f_FP = SR/(π·V_pp)Antenna Length Calculator (λ/4 · λ/2 · 5/8λ)
Compute free-space wavelength and the practical size of monopole, dipole, whip and loop antennas, including the velocity factor — before you cut wire or draw a PCB antenna.
λ = 300/f(MHz) m | monopole ≈ λ/4 × velocity factorused 2 timesVSWR / Return Loss Converter
Convert between VSWR, return loss, reflection coefficient, mismatch loss and transmitted power — the usual first step with a VNA reading or antenna datasheet.
Γ = (VSWR−1)/(VSWR+1) | RL = −20·log₁₀|Γ| | mismatch loss = −10·log₁₀(1−|Γ|²)dBm ⇄ mW ⇄ Voltage Converter
Convert between power level, milliwatts, RMS and peak-to-peak voltage (50Ω/75Ω selectable) — transmit power, receiver sensitivity and attenuation chains alike.
P(dBm) = 10·log₁₀(P/1mW) | V_rms = √(P·Z₀)STM32 Timer PSC / ARR Calculator
From the timer clock and target frequency or period, get prescaler PSC and auto-reload ARR plus the values to write to the registers and the resulting error.
f_out = f_clk / [(PSC+1)(ARR+1)]PID Parameter Conversion (Kp/Ti/Td ⇄ Discrete)
Turn ideal-form Kp/Ti/Td into positional and incremental discrete coefficients so you never hand-derive them in code again.
Ki = Kp/Ti | Kd = Kp·Td | discrete Ki = Kp·Ts/TiFirst-Order Low-Pass Filter Coefficient (α)
From sample period and cut-off, get the first-order IIR coefficient α, the fixed-point Q coefficient and settling time — ready to paste into ADC smoothing code.
α = Ts/(RC + Ts), RC = 1/(2πf_c); y += α(x − y)used 6 timesSpeaker Crossover Calculator (1st/2nd Order)
From driver impedance and crossover frequency, get the woofer series inductor / shunt capacitor and tweeter series capacitor / shunt inductor, with one-click first/second order and standard Q values.
2nd order: C = Q/(2πf_c·R) | L = R/(2πf_c·Q) | 1st order: L = R/(2πf_c), C = 1/(2πf_c·R)used 2 timesPCB Panel Utilization Calculator
From board size, panel size and spacing, get the number of boards per panel and the area utilisation — check it before quoting or designing V-cuts.
n = ⌊(L+spacing)/(l+spacing)⌋ × ⌊(W+spacing)/(w+spacing)⌋used 4 timesStencil Area Ratio & Paste Volume
From pad size and stencil thickness, compute area ratio, aspect ratio and paste volume to predict insufficient paste on fine-pitch pads — a DFM self-check.
Area ratio = W·L / [2T(W+L)] ≥ 0.66 | aspect ratio = W/T ≥ 1.5Substrate Current Capacity Calculator (AlN vs FR4)
Compares the maximum current a trace of the same geometry can carry on an aluminium-nitride versus an FR4 substrate using a 1D conduction model, and spells out voltage drop, drop ratio and dissipation — AlN’s high thermal conductivity raises the current capacity by an order of magnitude.
I = W·√(ΔT·k·T/(ρ·h)),ΔV = I·ρ·L/(W·t),δ = √(ρ/(π·f·μ))Copper Busbar Ampacity Calculator (Heat-Balance Method)
Solves copper busbar ampacity from the heat balance between I²R heating and convection/radiation cooling: size the current from bar width and thickness, or back-solve the minimum width for a given current and snap it to standard sizes, with current density, resistance/loss/drop per metre and AC skin-effect correction.
I = √(h·P·ΔT·A/ρ(T)), ρ(T) = ρ₂₀·[1+α(T−20)]used 10 timesBusbar (Multi-Branch Collection) Calculator
Collects several branch currents onto one main busbar: from the total current and design margin it gives cross-section, current density, full-length resistance, voltage drop, conductor and joint losses, estimated temperature rise, and a short-circuit thermal check.
R = ρ(T)·L/A | P = I²·(R + R_contact) | ΔT = P/(h·2(W+T)·L) | A_min = I_sc·√t/kused 1 timesCAN / CAN FD Bit Timing Calculator
Work out BRP, tq per bit, sample point and segment split from the CAN clock and target bitrate, plus the real bitrate error — before you touch the BTR registers.
Bitrate = f_clk / [BRP × (1 + tseg1 + tseg2)]RS-485 Termination & Bias Resistor Calculator
From node count and unit loads, compute the parallel termination, fail-safe bias resistors, bias current and the maximum line length for the bitrate — the first thing to check when an idle bus drifts or frames go missing.
V_AB = Vcc·Rp/(2Rb + Rp) ⇒ Rb = (Vcc·Rp/V_AB − Rp)/2used 12 timesCRC / LRC / Checksum Calculator
Paste a hex frame and get CRC16 (MODBUS / CCITT / XMODEM / IBM), CRC8, CRC32, LRC, XOR and sum checks, with the checksum bytes appended to the frame.
CRC-16/MODBUS: init FFFF, reflected polynomial A001, low byte firstused 8 timesHEX ⇄ ASCII ⇄ Decimal Converter
Convert between hex frames, text and decimal bytes, with byte count and non-printable characters — the most common first step in serial protocol debugging.
ASCII code = byte value; hex uses two digits per byte, 0x41 = "A"I²C Pull-up & Bus Rise Time Checker
Check whether the rise time from pull-up and bus capacitance meets the I²C spec, and back out the maximum capacitance and pull-up current — for when the waveform will not climb.
t_r ≈ 0.8473·R_p·C_bus (30%→70% of Vdd)SPI Clock & Timing Margin Checker
From slave setup/hold times and round-trip delay, check whether the current SCLK still keeps timing margin and derive the highest usable clock.
T_SCLK ≥ t_SU + t_H + t_PD (round trip)4–20 mA Current Loop Converter
Convert loop current to engineering units (temperature, pressure, level) and back, with percentage, sense-resistor drop and wire-break detection.
Value = LRV + (I − 4mA)/16mA × (URV − LRV)used 2 timesNTC Thermistor Temperature Calculator
Two-way B-equation conversion between temperature and resistance, plus reverse calculation from a pull-up + ADC reading, with sensitivity and ADC resolution.
R = R25·e^{B(1/T − 1/T25)} | 1/T = 1/T25 + ln(R/R25)/Bused 6 timesPT100 / PT1000 RTD Converter
Two-way platinum resistance conversion per IEC 60751 (Callendar–Van Dusen), with sensitivity and lead-resistance error estimates.
R(T) = R0[1 + A·T + B·T² (+ C(T−100)T³)], A = 3.9083e−3used 2 timesThermocouple mV ↔ Temperature (Cold-Junction Compensated)
Convert thermocouple EMF to temperature for K/J/T/E types with cold-junction compensation — forgetting this step is why a meter reading can be tens of degrees off.
E(T_hot) = E_meas + E(T_cold), then look up the tablePLC Analog Scaling (27648 / 32767 / 4000)
Two-way conversion between PLC analog codes and engineering values for Siemens 27648, generic 32767 and Mitsubishi/Omron 4000 full scales, with wire-break and over-range detection.
Value = LRV + (code/full-scale code × signal span − signal low)/(signal span) × (URV − LRV)Load Cell Output & Gain Calculator
From mV/V sensitivity and excitation, compute bridge output at full scale and at the current load, the gain needed and the ADC bits required — before wiring up an HX711 or ADS1232.
V_out = V_ex × sensitivity (mV/V) × load / capacityHeatsink Thermal Resistance & Junction Temperature
From dissipation, ambient temperature and package thermal resistance, find the θsa the heatsink must achieve and back-calculate junction temperature with the heatsink you have.
θsa,max = (Tj,max − Ta)/Pd − θjc − θcsused 3 timesFan Airflow Conversion & Air-Power Calculator
Convert between CFM, m³/h and L/s, compute air power from static pressure and fan efficiency, and back out the airflow needed to carry away a given heat load.
P_fan = Q·ΔP/η | ΔT = P/(ρ·c_p·Q)AC Power / Power Factor
Active / reactive / apparent power from voltage, current and power factor, auto-switching single/three phase.
P = UI·cosφ | 3-phase S = √3·U·I | Q = S·sinφThree-phase / Single-phase Power (Supply Standards)
Calculate apparent, active and reactive power, line and phase current for single-phase or balanced three-phase loads using national/regional supply standards (China 220/380 V, Europe 230/400 V, US 120/277/480 V, Japan 100/200 V…) or a custom voltage — and work back from power to current.
Three-phase S = √3·U_L·I_L | single-phase S = U·I | P = S·cosφ | Q = S·sinφused 65 timesMotor Rated Current
Rated current from power, efficiency, and power factor, with the "≈2A per kW at 380V 3-phase" rule-of-thumb check.
I = P / (√3·U·η·cosφ) (three-phase)Transformer Ratio / Turns
Turns ratio from primary/secondary voltage; enter either side’s turns to derive the other.
U1/U2 = N1/N2 = kTransformer Capacity ↔ Rated Current
Primary/secondary rated current from kVA and voltage level — for breaker selection and protection settings.
I = S / (√3·U) (3-phase) | single-phase I = S / UVoltage Drop / Wire Size Check
Voltage drop percentage from conductor material and cross-section, and the minimum section for an allowed drop — essential for long runs.
ΔU = 2·I·L·ρ/S (single-phase) | √3·I·L·ρ/S (three-phase)used 1 timesWire Cross-Section (Current)
Estimate cross-section from load current and rule-of-thumb current density, rounded to standard sizes.
S = I / J (J: copper open 6 / conduit 5 A/mm²; aluminum one tier lower)used 3 timesReactance (XL / XC)
Inductive and capacitive reactance at line (or any) frequency, to guide compensation and filtering.
XL = 2πfL | XC = 1/(2πfC)used 1 timesReactive Power Compensation
Required kvar from current to target power factor — the cure for power-factor penalties.
Qc = P · (tanφ1 − tanφ2)Energy / Electricity Cost
Energy and cost from power and runtime; compare before/after efficiency upgrades at a glance.
W = P · t (kWh) | cost = W × rateStar ↔ Delta Resistor Conversion
Simplify balanced three-phase networks: Y↔Δ resistor conversion for unbalanced networks.
Y→Δ: RΔ = R1+R2+R1R2/R3 | Δ→Y: RY = adjacent product/ΣRused 2 timesMotor Sizing (Load Torque)
Size AC induction, DC, or brushed/brushless motors by load profile (constant torque / power / quadratic / shock): power, standard tier rounding, torque and overload check.
P_L = T_L·n_L/9550 | P_N ≥ K·P_L/η_t | T_N = 9550·P_N/n_N | peak ≤ λ·T_NBuck step-down design
Enter design targets (voltage range / temperature rise / ripple / mode / frequency) to get the inductor, input/output capacitors, MOS SOA, gate resistor, and thermal design in one go.
D = Vout/Vin | L = (Vin−Vout)·D/(ΔIL·fsw)used 2 timesBoost step-up design
Enter design targets to get the inductor (with RHP-zero check band), input/output capacitors, MOS SOA, gate resistor, and thermal design.
D = 1−Vin/Vout | L = Vin·D/(ΔIL·fsw)used 30 timesBuck-Boost step-up/down design
Enter design targets (output taken as absolute value, polarity inverted) to get the inductor, input/output capacitors, MOS SOA, gate resistor, and thermal design.
D = |Vout|/(Vin+|Vout|) | L = Vin·D/(ΔIL·fsw)used 12 timesRC Snubber Design
Ring damping for MOS / relay switching nodes: dual-frequency extraction of strays, with R/C values, loss, and an impedance Bode plot.
f_ring = 1/(2π√(LC)) | R = √(L/C) | Cs = 2~3Cp | P = Cs·ΔV²·fswused 72 timesRCD / RDC Clamp Snubber Design
RCD clamp for flyback leakage spikes: clamp resistor / capacitor / ultrafast diode values, loss, and drain stress.
R = 2Vc(Vc−Vro)/(Llk·Ipk²·fsw) | C = Vc/(R·ΔV·fsw) | P = ½Llk·Ipk²·fsw·Vc/(Vc−Vro)used 1 timesModbus RTU Frame & CRC16
Pack/unpack Modbus RTU frames (master request / slave response), compute the CRC-16/MODBUS checksum, and decode frames — matched against the standard frame format.
Frame = Slave + Function + Data + CRC16 (low byte first) | CRC-16/MODBUS init 0xFFFFused 5 timesModbus TCP Frame & MBAP
Pack/unpack Modbus TCP frames (master request / slave response) with MBAP header decoding, protocol-ID and length self-checks — matched against the standard frame format.
Frame = MBAP (Transaction ID + Protocol ID + Length + Unit ID) + Function + DataFrequency–Wavelength Calculator
Frequency ↔ wavelength conversion: vacuum/medium wavelength, period, velocity factor, half/quarter-wave antenna sizes, and photon energy.
λ = c / f | in medium λ′ = c / (f·√εr) | T = 1 / fused 2 timesRipple Filter Capacitor Calculator
Compute the required filter capacitance from ripple current, ripple frequency and allowed ripple: mains rectifier (full/half-wave), buck output triangular ripple, and sinusoidal ripple.
C = I / (K·f·ΔV) | full-wave K=2 · half-wave K=1 · buck K=8 · sine K=2πused 7 timesDecibel (dB) Calculator
Convert ratios, power and voltage to and from decibels: power ratio ↔ dB, voltage ratio ↔ dB, absolute power (dBm / dBW), voltage level (dBV / dBu / dBμV) and cascaded gain.
dB = 10·log10(P2/P1) = 20·log10(V2/V1) | dBm = 10·log10(P/1mW)used 10 timesCelsius ↔ Fahrenheit Temperature Converter
Convert between Celsius (°C), Fahrenheit (°F), Kelvin (K) and Rankine (°R): enter any one scale to get the other three, with an absolute-zero check.
°F = °C × 9/5 + 32 | K = °C + 273.15 | °R = K × 9/5used 1 timesHysteresis Comparator (Schmitt Trigger)
Comparator positive-feedback hysteresis network: for the inverting / non-inverting topologies, derive the upper and lower trip points and hysteresis width from R1/R2 and the output swing, bound the width / trip-point error with the resistor tolerance, or pick standard resistors and a reference voltage from target trip points.
ΔV = (Voh − Vol)·R1/(R1+R2) (inverting) | ΔV = (Voh − Vol)·R1/R2 (non-inverting)used 38 timesNon-inverting op-amp calculator
Non-inverting op-amp stage: derive the voltage gain from Rf/Rg, or pick standard resistors for a target gain, then use the resistor tolerance to bound the gain error, and check gain-bandwidth and slew-rate limits (closed-loop bandwidth, full-power bandwidth, rise time).
A = 1 + Rf/Rg | BW = GBW / A | SR = 2π·f·Vpk | FPBW = SR / (2π·Vpk) | A_range = 1 + Rf(1±t)/Rg(1∓t)Differential op-amp calculator
Four-resistor difference (subtractor) amplifier: compute the output, differential gain, common-mode gain and CMRR from R1–R4 and two inputs, bound the gain / output error and worst-case CMRR with the resistor tolerance, or match standard resistors to a target gain, and check input impedance, bandwidth and slew rate.
Vout = V2·R4/(R3+R4)·(1+R2/R1) − V1·R2/R1 | when matched, Vout = Ad·(V2−V1), Ad = R2/R1used 3 timesInverting op-amp calculator
Inverting op-amp stage: derive the voltage gain (A = −Rf/Rin) and input impedance from Rf/Rin, or pick standard resistors for a target gain, then use the resistor tolerance to bound the gain / output error and maximum mismatch error, and check noise-gain bandwidth and slew rate.
A = −Rf/Rin (|A| = Rf/Rin) | Zin = Rin | BW = GBW/(1+|A|) | SR = 2π·f·Vpk | FPBW = SR/(2π·Vpk)BPF op-amp band-pass filter designer (single-op-amp Sallen-Key)
Single-op-amp Sallen-Key band-pass filter (BPF) designer: given the high-pass / low-pass corner frequencies (fL, fH) or the center frequency and bandwidth (f0, BW), it automatically picks C1 and R4 and derives every R/C value, with standard-value rounding plus slew-rate and GBW checks and a Bode plot.
Auto C1 (so R1 ≈ 33 kΩ) | k = 2π·f0·C1 | H = (6.5 − 1/Q)/3 | C2 = C1/2 | R1 = 2/k, R2 = 2/(3k), R3 = 4/k, R5 = R4/(H−1) (auto R4 so R5 ≈ 10 kΩ) | Q = f0/BWused 14 timesOp-amp voltage-controlled resistor (VCR) designer
Single-op-amp voltage-controlled resistor (VCR) designer: a JFET (or a MOSFET in its ohmic region) acts as the variable resistor R_DS in the feedback path of an inverting amplifier, with an AN105 linearization network (equal R_L1/R_L2 across D-G and S-G) that decouples R_DS from the signal level and keeps the pass device in its ohmic region. Compute the equivalent resistance and voltage-controlled gain from the control voltage, or Vc from a target resistance, with linear-swing, sensitivity and bandwidth checks.
JFET: R_DS = V_P² / [2·I_DSS·(V_GS − V_P)] | MOSFET: R_DS = 1 / [k·(V_GS − V_TH)] | V_GS = Vc − V_S ≈ Vc (virtual-ground source) | A = −R_DS / Rg | |V_DS| < V_GS − V_th (R_L1 = R_L2 linearization)Impedance matching calculator (L / π / T)
Online design of L, π and T matching networks for RF and antennas: enter the source impedance Rs+jXs and load impedance RL+jXL to get the network Q, inductor and capacitor values, the approximate −3 dB bandwidth, and a circuit diagram of the chosen topology. Complex source / load reactances are compensated.
L: Q = √(Rhigh/Rlow − 1), Xseries = Q·Rlow, Bshunt = Q/Rhigh | π: Rv = Rhigh/(Q²+1), Xseries = Rv(Q1+Q2) | T: Rv = Rlow(Q²+1), Xseries = Q·R | elements: L = X/ω, C = 1/(ωX)used 53 timesUnit Converter
Convert between units of length, area, volume, mass, pressure, force, energy, power, speed, time and temperature, plus common electrical quantities such as voltage, current, resistance, capacitance, inductance, frequency and charge: pick the from and to units to get the result, with a full comparison of every unit in the same quantity.
target = source × k_from ÷ k_to | temperature: °F = °C × 9/5 + 32used 136 timesNewton's Second Law Calculator (F=ma)
Compute the net force via F = m·a: enter mass and acceleration to get the force, with the weight W = m·g shown for reference.
F = m·a | Weight W = m·g (g = 9.80665 m/s²)Pressure Calculator (P=F/A)
Compute pressure via P = F/A: enter the force and contact area to get results in Pa, kPa and MPa.
P = F / ATorque Calculator (τ=F·r·sinθ)
Compute the moment about an axis via τ = F·r·sinθ: enter force, lever arm and angle to get N·m and the effective lever arm.
τ = F·r·sinθWork Calculator (W=F·d·cosθ)
Compute work via W = F·d·cosθ: enter force, displacement and angle to get joules and kWh.
W = F·d·cosθMechanical Power Calculator (P=F·v)
Compute the instantaneous power of a traction force at constant velocity via P = F·v: enter force and speed to get W, kW and horsepower.
P = F·vKinetic Energy Calculator (Ek=½mv²)
Compute kinetic energy via Ek = ½mv²: enter mass and velocity to get joules and the equivalent drop height.
Ek = ½·m·v²Gravitational Potential Energy Calculator (Ep=mgh)
Compute gravitational potential energy via Ep = mgh: enter mass and height to get joules and the landing velocity.
Ep = m·g·hMomentum Calculator (p=mv)
Compute momentum via p = m·v: enter mass and velocity to get kg·m/s, with kinetic energy and equivalent impulse for reference.
p = m·vImpulse Calculator (J=F·Δt)
Compute impulse via J = F·Δt: enter force and duration to get N·s and the resulting momentum change.
J = F·ΔtSpring Force Calculator (Hooke's Law F=kx)
Compute spring force via Hooke's law F = k·x: enter stiffness and deformation to get the force and stored energy.
F = k·xElastic Potential Energy Calculator (Ep=½kx²)
Compute elastic potential energy via Ep = ½kx²: enter stiffness and deformation to get joules and the maximum release velocity.
Ep = ½·k·x²Spring-Mass Oscillator Period Calculator (T=2π√(m/k))
Compute the simple harmonic period via T = 2π√(m/k): enter mass and stiffness to get period, frequency and angular frequency.
T = 2π·√(m/k)Pendulum Period Calculator (T=2π√(L/g))
Compute the pendulum period via T = 2π√(L/g): enter length and gravity to get period and frequency (small-angle approximation).
T = 2π·√(L/g)Centripetal Force Calculator (F=mv²/r)
Compute the centripetal force via F = mv²/r: enter mass, velocity and radius to get the force and centripetal acceleration.
F = m·v²/r = m·ω²·rLinear & Angular Velocity Calculator (v=ωr)
Compute linear velocity via v = ω·r = 2πn·r/60: enter rotational speed and radius to get linear and angular velocity.
v = ω·r = 2π·n·r/60Torque-RPM-Power Calculator (P=τ·n/9549)
Convert motor torque, speed and power via P(kW) = τ(N·m)·n(rpm)/9549: pick any two known values to solve the third.
P = τ·n/9549 (P: kW · τ: N·m · n: rpm)Gear Ratio Calculator (i=z₂/z₁)
Compute the gear ratio via i = z₂/z₁: enter driving/driven tooth counts and input speed to get ratio, output speed and torque multiplication.
i = z₂/z₁ = n₁/n₂ = τ₂/τ₁Density Calculator (ρ=m/V)
Compute density via ρ = m/V: enter mass and volume (multiple units) to get kg/m³ and g/cm³, compared against water.
ρ = m / VFriction Force Calculator (f=μN)
Compute friction via f = μ·N: enter the coefficient and normal force (from direct input, mass or an incline) to get static/kinetic friction.
f = μ·NBuoyancy Calculator (Archimedes F=ρgV)
Compute buoyancy via Archimedes' principle F = ρ·g·V: enter liquid density and displaced volume.
F = ρ·g·VIdeal Gas Law Calculator (PV=nRT)
Solve any one of pressure, volume, amount of substance or temperature from the ideal gas law PV = nRT, with Pa/kPa/bar/atm and m³/L/cm³/K/°C units.
PV = nRT | R = 8.314 J/(mol·K)Boyle's Law Calculator (P₁V₁=P₂V₂)
In an isothermal process, gas pressure is inversely proportional to volume: given the initial pressure/volume and one final quantity, solve the other (temperature constant).
P₁V₁ = P₂V₂ (isothermal process, T constant)used 1 timesCharles's Law Calculator (V₁/T₁=V₂/T₂)
In an isobaric process, gas volume is proportional to absolute temperature: given any three of the initial/final volume/temperature, solve the fourth (pressure constant).
V₁/T₁ = V₂/T₂ (isobaric process, P constant)Gay-Lussac's Law Calculator (P₁/T₁=P₂/T₂)
In an isochoric process, gas pressure is proportional to absolute temperature: given any three of the initial/final pressure/temperature, solve the fourth (volume constant).
P₁/T₁ = P₂/T₂ (isochoric process, V constant)Specific Heat Calculator (Q=mcΔT)
Compute the heat absorbed or released when an object heats or cools via Q = m·c·ΔT, with results in joules / kilojoules / kilocalories and common material specific-heat references.
Q = m·c·ΔTLatent Heat Calculator (Q=mL)
Compute the heat absorbed or released during a phase change (melting / freezing / vaporization / condensation) via Q = m·L.
Q = m·LHeat Conduction Calculator (Fourier Q=kAΔT/L)
Compute steady heat conduction through a plate/wall via Fourier’s law Q = k·A·ΔT/L, with thermal resistance and heat flux per unit area.
Q = k·A·ΔT / LConvection Calculator (Newton’s Cooling Q=hAΔT)
Compute convective heat transfer between a solid surface and a fluid via Newton’s law of cooling Q = h·A·(Ts − T∞), covering common natural/forced convection coefficients.
Q = h·A·(Ts − T∞)Thermal Radiation Calculator (Stefan–Boltzmann Q=εσAT⁴)
Compute thermal radiation power via the Stefan–Boltzmann law Q = ε·σ·A·T⁴, and enter the surroundings temperature to get net radiative heat transfer.
Q = ε·σ·A·T⁴ | σ = 5.67×10⁻⁸ W/(m²·K⁴)Linear Thermal Expansion Calculator (ΔL=αL₀ΔT)
Compute linear expansion ΔL = α·L₀·ΔT and the expanded length for pipes, structures and precision parts.
ΔL = α·L₀·ΔTVolume Thermal Expansion Calculator (ΔV=βV₀ΔT)
Compute volume expansion ΔV = β·V₀·ΔT and the expanded volume; for solids β ≈ 3α, and liquids use their volume expansion coefficient.
ΔV = β·V₀·ΔT | solid β ≈ 3αMechanical Equivalent of Heat Calculator (W=J·Q)
Convert between heat (calories) and mechanical work (joules): 1 cal = 4.1868 J, for estimating thermal–mechanical energy conversion.
W = J·Q | J = 4.1868 J/calCarnot Efficiency Calculator (η=1−Tc/Th)
Compute the maximum efficiency of an ideal Carnot engine operating between hot reservoir Th and cold reservoir Tc, plus the Carnot refrigerator / heat pump coefficients.
η = 1 − Tc/Th (absolute temperature K)Heat Engine Efficiency Calculator (η=W/Qh)
Compute real heat engine efficiency η = W/Qh: given any two of heat input, heat rejection and work output, solve the third and the efficiency.
η = W / Qh = (Qh − Qc) / QhRefrigeration COP Calculator (COP=Qc/W)
Compute the refrigeration coefficient of performance COP = Qc/W: given cooling capacity and work input, output the COP and heat rejected to the hot side.
COP = Qc / WHeat Pump COP Calculator (COPₕ=Qh/W)
Compute the heat pump coefficient of performance COPₕ = Qh/W: given heating capacity and work input, output the COPₕ and heat absorbed from the cold side.
COPₕ = Qh / W = 1 + Qc/WEntropy Change Calculator (ΔS=Q/T)
Compute entropy change ΔS = Q/T for a reversible isothermal process: enter heat transfer and process temperature to get J/K and kJ/K.
ΔS = Q / T (reversible isothermal process)First Law of Thermodynamics Calculator (ΔU=Q−W)
Solve internal energy change, heat absorbed or work done via the first law ΔU = Q − W (energy conservation).
ΔU = Q − WGas Specific Heat & Adiabatic Index Calculator (γ=Cp/Cv)
Compute the relationship among constant-pressure Cp, constant-volume Cv and adiabatic index γ for an ideal gas, and verify Mayer’s relation Cp−Cv=R.
γ = Cp/Cv | Cp − Cv = RMixture Temperature Calculator (Thermal Equilibrium)
Compute the final temperature when two substances reach thermal equilibrium: m₁c₁(T₁−T) = m₂c₂(T−T₂), with the heat exchanged.
T = (m₁c₁T₁ + m₂c₂T₂) / (m₁c₁ + m₂c₂)coulomb定律Calculate器
liang静止点电荷间静电Force:F = k·q1·q2 / r²,同号相斥、异号相吸。
F = k·q1·q2 / r² | k = 1/(4πε0) ≈ 8.988×10⁹ N·m²/C²点电荷电场强度Calculate器
点电荷在空间某点的电场强度:E = k·Q / r²,正电荷向外、负电荷向里。
E = k·Q / r² = F / q | 1 N/C = 1 V/m点电荷电势and电势能Calculate器
点电荷的电势 V = k·Q / r,试探电荷的电势能 U = q·V(标量,带符号)。
V = k·Q / r | U = q·V平行板Capacitance器Calculate器
平行板Capacitor C = εr·ε0·A / d,并给出Charge后Electric charge、储能and板间场强。
C = εr·ε0·A / d | Q = C·V | E = ½C·V² | E场 = V / dCapacitance储能Calculate器
Capacitance储存的Energy E = ½·C·V² = ½·Q·V,以及充满时Electric charge。
E = ½·C·V² = ½·Q·V | Q = C·Vused 1 timesResistanceandResistance率Calculate器
由Resistance率求导线Resistor R = ρ·L / A,或由Resistance反推材料Resistance率。
R = ρ·L / A | A = π·(d/2)²带电粒子电场加速Calculate器
带电粒子经电势差 U 加速后的Speedand动能:v = √(2·q·U/m)。
v = √(2·q·U / m) | Ek = q·U电Powerand电能Calculate器
直流电路Power P = V·I,and用电时长一startConversion电能(J / kWh)。
P = V·I | W = P·t | 1 kWh = 3.6×10⁶ JCurrentandElectric chargeCalculate器
Current、Electric chargeandTime互算:I = Q / t,并折算为Pass的电子数。
I = Q / t | N = Q / ejoule定律Calculate器
CurrentPassResistance产生的Heat Q = I²·R·t(joule热),Conversion为calorie路里。
Q = I²·R·t | 1 cal = 4.184 J直导线磁场Calculate器
无限长载流直导线周围磁感应强度:B = μ0·I / (2πr)。
B = μ0·I / (2πr) | μ0 = 4π×10⁻⁷ N/A²螺线管磁场Calculate器
长直螺线管内部匀强磁场:B = μ0·(N/L)·I,含铁芯时乘 μr。
B = μr·μ0·n·I | n = N/L(turns密度)环形CurrentMedium心磁场Calculate器
载流Circle环(N turns)Circle心处磁感应强度:B = μ0·N·I / (2R)。
B = μ0·N·I / (2R)洛伦兹ForceCalculate器
带电粒子垂直进入磁场所受洛伦兹Force F = q·v·B,并给出回旋半径andPeriod。
F = q·v·B | r = m·v / (q·B) | T = 2πm / (q·B)ampere培ForceCalculate器
磁场Medium载流直导线所受ampere培Force:F = B·I·L·sinθ。
F = B·I·L·sinθ磁通量Calculate器
穿过某Area的磁通量 Φ = B·A·cosθ(匀强磁场)。
Φ = B·A·cosθfarad拉第电磁感应Calculate器
磁通量变化产生的感应电动势:ε = N·ΔΦ/Δt(大小)。
ε = N·ΔΦ / Δt动生电动势Calculate器
导体棒在磁场Medium切割磁感线产生的电动势:ε = B·L·v。
ε = B·L·v(B ⊥ L ⊥ v 时)自感andInductance储能Calculate器
自感系数 L = N·Φ / I,及Inductance储存的磁场能 E = ½·L·I²。
L = N·Φ / I | E = ½·L·I²RL 电路Time常数Calculate器
RL Series电路Time constant τ = L/R,及上电后任意时刻的Current。
τ = L/R | i(t) = (V/R)·(1 − e^(−t/τ))芯片发热 / 结温Calculate器
按芯片dissipationand「结 → 壳 → 散热器 → Surroundings」热阻链,Calculate结温、壳温and散热器Temperature,并对比无散热器方案、校核最HighJunction margin。
θJA(总) = θJC + θCS + θSA | Tj = Ta + P × θJA | Tc = Tj − P × θJCused 19 timesZener Diode Series Resistor
Design the series resistor for a Zener shunt regulator from the input range, Zener voltage, and load current, and check Zener current, power, and light-load / full-load / maximum-input conditions.
R = (Vin − Vz)/(Iz + Iload) | P_R = (Vin − Vz)²/R | Pz = Vz·IzTVS Diode Selection
Select a TVS from the protected circuit maximum operating voltage, downstream withstand voltage, and surge current; check standoff voltage, clamping voltage, peak pulse power, and rated surge-current margin.
Vc = Vbr + Ipp·(Vc_rated − Vbr)/Ipp_rated | Ppp = Vc·Ipp | E ≈ Vc·Ipp·tpused 8 timesFuse Selection
Choose a fuse rating from continuous load current, ambient temperature, and surge I²t; check derating, melting integral, and voltage rating to avoid nuisance blowing.
In ≥ Iload/(derating × temperature factor) | I²t_fuse ≥ 2 × I_inrush²·t_inrushLM317 Adjustable Regulator Resistors
LM317 / LM1117-ADJ design: solve R2 for the target output, check actual output, minimum load, dropout, and junction temperature, with R1 / R2 dissipation.
Vout = Vref·(1 + R2/R1) + Iadj·R2 | P = (Vin − Vout)·Iload | Tj = Ta + P·θJABJT Voltage-Divider Bias
Resistor-divider bias for an NPN common-emitter stage: solve R1/R2/Rc/Re from Vcc, target Ic, hFE, and collector / emitter voltages, then check the operating point, gain, and I/O impedance.
Ve = Ie·Re | Vb = Ve + Vbe | R1/R2 set by 10×Ib divider current | Av ≈ Rc/ReRC Charge / Discharge Time
First-order RC charge / discharge: compute the time constant, time to the target voltage, and the 63.2% / 95% / 99% and half-life points.
τ = R·C | charge t = −τ·ln(1 − Vt/Vs) | discharge t = −τ·ln(Vt/Vs)used 8 timesCrystal Load Capacitor
Crystal load-cap design: solve C1 / C2 from the specified CL and PCB / pin stray capacitance, or back-calculate actual CL and frequency pulling.
CL = C1·C2/(C1+C2) + Cstray | symmetrical C1 = C2 = 2(CL − Cstray) | Δf/f ≈ −Cm·ΔCL/(2(C0+CL)²)I2C Pull-Up Resistor
I2C bus pull-up: compute Rp_max / Rp_min from bus capacitance, speed, and device sink current; recommend an E24 value and check rise time and low level.
Rp(max) = tr/(0.8473·Cb) | Rp(min) = (Vdd − Vol)/Iol | tr = 0.8473·Rp·Cbused 1 timesMOSFET Gate Resistor
Compute the external gate resistor from drive voltage, gate charge, Miller charge, and target switching time; check peak drive current, drive power, and resistor dissipation.
Rg_ext = Vdrive·t_sw/Qgd − Rg_int | Ipk = Vdrive/(Rg_ext + Rg_int) | P_drive = Qg·Vdrive·fswused 9 timesMOSFET Switching Loss
MOSFET loss breakdown: conduction, switching overlap, Coss, gate drive, and reverse recovery, plus junction-temperature estimate for selection and thermal design.
P_cond = I²·Rds(on)·D | P_sw = ½·Vds·Id·(tr+tf)·fsw | P_coss = ½·Coss·Vds²·fswused 3 timesMOS 管实际可用Current(结温反推)
给定 R_DS(on)、Temperature系数、允许结温andSurroundings热阻,反推这颗 MOS 管在本机Cooling condition下能连续过多大Current。R_DS(on) 随结温literHigh而变大,本工具做自洽迭代,并给出指定工作Current下的Junction marginand所需热阻。
Imax = √[(Tj,max − Ta − P_other·θJA) / (θJA·R_DS(on)(Tj,max))] | R_DS(on)(Tj) = R25·[1 + α(Tj − 25)]used 86 timesTVS 浪涌钳bitsandEnergy校核
填被保护器件的最High工作Voltage、绝对最大额定and浪涌威胁(手填Current、SourceVoltage/阻抗,或 IEC 61000-4-2 ESD / IEC 61000-4-4 EFT 标准),自动推荐pass钳bits窗口的 SMAJ / SMBJ / SMCJ 型号and ESD 关键参数;也可反过来校核你手上那颗 TVS 的钳bits、Energy、结温and闩锁风险。
I = (Uoc − Vbr)/(Rs + Rd) | Rd = (Vc − Vbr)/Ipp | τ = t_half/ln2 | E = Vc·Ipk·τ | Tj = Ta + E·f·Rth | 推荐:V_RWM ≥ 1.1·Vop、V_BR > Vop、V_C(I) ≤ 0.8·V_absused 695 timesAWG ↔ Metric Cross-Section
Convert between AWG, metric cross-section, conductor diameter, and resistance per kilometre, with a current-density ampacity estimate.
d = 0.127·92^((36−n)/39) | S = πd²/4 | R = ρ·1000/SMotor Speed / Poles / Slip
Find synchronous speed from supply frequency and pole count, then actual speed from slip; or back-calculate slip and slip frequency from measured speed.
n_s = 120f/p | s = (n_s − n)/n_s | f₂ = s·fStar-Delta Starting Current / Torque
Compare direct-on-line and star-delta starting line current, starting torque, and star phase voltage; check whether the load can start.
I_Y = I_Δ/3 | T_Y = T_Δ/3 | U_phase,Y = U_line/√3Circuit Breaker Selection
Select a miniature circuit breaker from load current, ambient temperature, and trip curve; check cable ampacity and motor-start inrush.
I_n ≥ K·I_load/temperature factor | I_n ≤ I_z (cable ampacity) | magnetic trip > inrushContactor / Thermal Overload Relay Selection
Select an AC-3 contactor and thermal-relay setting range from motor rated current, and recommend the trip class from starting time.
I_KM ≥ I_e | I_FR ≈ I_e | trip class 10 / 20 / 30 by starting timeCT / Meter Multiplier
Compute the meter multiplier from CT primary/secondary current and PT ratio, then convert secondary current / meter reading to primary current and energy.
K_CT = I₁/I₂ | multiplier = K_CT·K_PT | W₁ = W₂·multiplierTransformer Short-Circuit Current
Estimate secondary symmetrical short-circuit current, short-circuit capacity, and peak current from transformer rating, secondary voltage, and impedance voltage for switchgear breaking checks.
I_sc = S/(√3·U·u_k) | S_sc = S/u_k | i_p ≈ √2·I_sc·(1+e^(−π/(X/R)))Ground Resistance / Electrode
Estimate single-rod ground resistance from soil resistivity and electrode dimensions, then compute parallel resistance and the number of rods needed for the target.
R₁ = ρ/(2πL)·(ln(4L/d) − 1) | R_n = R₁/(n·η)Electric Heating Power / Connection
Compute heating power, phase current, and line current for single-phase / star / delta connection from voltage and per-phase resistance, or scale power with voltage.
P_star = U²/R | P_delta = 3U²/R | P₂ = P₁·(U₂/U₁)²Demand-Factor Load Calculation
Compute active / reactive / apparent load and design current from installed capacity, demand factor, simultaneity factor, and power factor; pre-select transformer capacity.
P_js = K_x·K_Σ·P_e | Q_js = P_js·tanφ | S_js = √(P²+Q²) | I_js = S_js/(√3·U)RCD (Residual Current Device) Selection
Select RCD rated current, residual operating current, and type from load current, protection purpose, and leakage; check cable ampacity and normal leakage.
I_n ≥ K·I_load/temperature factor | I_Δn ≥ 3×normal leakage | personnel protection I_Δn = 30 mAused 1 timesSPD (Surge Protective Device) Selection
Select SPD type, Uc, In/Imax, and Up from system voltage, grounding system, installation location, and equipment withstand; check lead length.
U_c ≥ 1.1·U₀ (1.5·U₀ for TT) | U_p,eff = U_p + L·1kV/m | U_p,eff ≤ U_wConduit / Tray Fill Selection
Compute the required conduit inner diameter from cable outer diameter, count, and bends; recommend a standard size and check actual fill and cable count.
A_cable = n·πd²/4 | A_req = A_cable/fill | D_req = √(4A_req/π)Cable Short-Circuit Thermal Check
Compute the minimum allowable cross-section from short-circuit current, protection clearing time, conductor, and insulation; check cable thermal withstand.
S_min = I_sc·√t / k | I_allow = k·S/√tused 3 timesCapacitor Current / Capacitance / Reactor Rate
From reactive compensation, compute capacitor phase current, per-phase capacitance, and rated voltage, with series reactor rate and resonant order.
Q_c = P·(tanφ₁ − tanφ₂) | C = Q_phase/(2πf·U_c²) | h = 1/√pVFD Selection
Select VFD power and current rating from motor power/current, load type, overload requirement, and ambient/altitude derating.
I_VFD ≥ I_e·K_overload/derating | P_VFD ≥ P_e·K/deratingUPS Capacity / Battery Backup
Select UPS capacity, battery string voltage, and battery capacity from critical load, power factor, and backup time; back-calculate actual backup time.
S_UPS ≥ P/(cosφ·loading) | C = P·t/(η·DoD·U_bat)Diesel Generator Sizing
Estimate diesel generator capacity from continuous load, largest motor starting method, and power factor; recommend common genset ratings.
S_continuous = P/cosφ×margin | S_start = P_motor×K_start | S_gen = max(S_continuous, S_start)Busbar / Copper Bar Selection
Estimate required busbar cross-section from rated current, material, parallel bars, and ambient temperature; recommend standard copper/aluminum sizes and check current density.
A_req = I/(J·n·temperature factor) | J_Cu ≈ 3 A/mm², J_Al ≈ 2 A/mm²used 10 timesMotor Protection Circuit Breaker (MPCB) Selection
Select MPCB frame, thermal-magnetic trip range, and breaking capacity from motor rated current, starting current, and prospective short-circuit current.
I_set ≈ I_e | magnetic trip ≈ 12×I_n | I_cu ≥ I_sc