198电子 / 电工 / 嵌入式 / 传感器 / Thermal Design / Mechanics / Thermodynamics / 电磁学High频Calculate器,SVG 图示Calculate模型,填参数即时出结果:Resistance分压、DC-DC 反馈Resistance、TL431 反馈(Flyback / Forward)、PCB 阻抗 / 载流、CAN bits定时、CRC check、4-20mA、NTC / PT100、PLC 模拟量、散热器选型、Battery stringandCharge、Sallen-Key 滤波器、传输线延时、VSWR、motor选型、线路voltage drop、calorie诺效率……

Electrical & AC

34 tools
Electrical & AC

Copper Busbar Ampacity Calculator (Heat-Balance Method)

Solves copper busbar ampacity from the heat balance between I²R heating and convection/radiation cooling: size the current from bar width and thickness, or back-solve the minimum width for a given current and snap it to standard sizes, with current density, resistance/loss/drop per metre and AC skin-effect correction.

I = √(h·P·ΔT·A/ρ(T)), ρ(T) = ρ₂₀·[1+α(T−20)]used 10 times
Electrical & AC

Busbar (Multi-Branch Collection) Calculator

Collects several branch currents onto one main busbar: from the total current and design margin it gives cross-section, current density, full-length resistance, voltage drop, conductor and joint losses, estimated temperature rise, and a short-circuit thermal check.

R = ρ(T)·L/A | P = I²·(R + R_contact) | ΔT = P/(h·2(W+T)·L) | A_min = I_sc·√t/kused 1 times
Electrical & AC

AC Power / Power Factor

Active / reactive / apparent power from voltage, current and power factor, auto-switching single/three phase.

P = UI·cosφ | 3-phase S = √3·U·I | Q = S·sinφ
Electrical & AC

Three-phase / Single-phase Power (Supply Standards)

Calculate apparent, active and reactive power, line and phase current for single-phase or balanced three-phase loads using national/regional supply standards (China 220/380 V, Europe 230/400 V, US 120/277/480 V, Japan 100/200 V…) or a custom voltage — and work back from power to current.

Three-phase S = √3·U_L·I_L | single-phase S = U·I | P = S·cosφ | Q = S·sinφused 65 times
Electrical & AC

Motor Rated Current

Rated current from power, efficiency, and power factor, with the "≈2A per kW at 380V 3-phase" rule-of-thumb check.

I = P / (√3·U·η·cosφ) (three-phase)
Electrical & AC

Transformer Ratio / Turns

Turns ratio from primary/secondary voltage; enter either side’s turns to derive the other.

U1/U2 = N1/N2 = k
Electrical & AC

Transformer Capacity ↔ Rated Current

Primary/secondary rated current from kVA and voltage level — for breaker selection and protection settings.

I = S / (√3·U) (3-phase) | single-phase I = S / U
Electrical & AC

Voltage Drop / Wire Size Check

Voltage drop percentage from conductor material and cross-section, and the minimum section for an allowed drop — essential for long runs.

ΔU = 2·I·L·ρ/S (single-phase) | √3·I·L·ρ/S (three-phase)used 1 times
Electrical & AC

Wire Cross-Section (Current)

Estimate cross-section from load current and rule-of-thumb current density, rounded to standard sizes.

S = I / J (J: copper open 6 / conduit 5 A/mm²; aluminum one tier lower)used 3 times
Electrical & AC

Reactance (XL / XC)

Inductive and capacitive reactance at line (or any) frequency, to guide compensation and filtering.

XL = 2πfL | XC = 1/(2πfC)used 1 times
Electrical & AC

Reactive Power Compensation

Required kvar from current to target power factor — the cure for power-factor penalties.

Qc = P · (tanφ1 − tanφ2)
Electrical & AC

Energy / Electricity Cost

Energy and cost from power and runtime; compare before/after efficiency upgrades at a glance.

W = P · t (kWh) | cost = W × rate
Electrical & AC

Star ↔ Delta Resistor Conversion

Simplify balanced three-phase networks: Y↔Δ resistor conversion for unbalanced networks.

Y→Δ: RΔ = R1+R2+R1R2/R3 | Δ→Y: RY = adjacent product/ΣRused 2 times
Electrical & AC

Motor Sizing (Load Torque)

Size AC induction, DC, or brushed/brushless motors by load profile (constant torque / power / quadratic / shock): power, standard tier rounding, torque and overload check.

P_L = T_L·n_L/9550 | P_N ≥ K·P_L/η_t | T_N = 9550·P_N/n_N | peak ≤ λ·T_N
Electrical & AC

AWG ↔ Metric Cross-Section

Convert between AWG, metric cross-section, conductor diameter, and resistance per kilometre, with a current-density ampacity estimate.

d = 0.127·92^((36−n)/39) | S = πd²/4 | R = ρ·1000/S
Electrical & AC

Motor Speed / Poles / Slip

Find synchronous speed from supply frequency and pole count, then actual speed from slip; or back-calculate slip and slip frequency from measured speed.

n_s = 120f/p | s = (n_s − n)/n_s | f₂ = s·f
Electrical & AC

Star-Delta Starting Current / Torque

Compare direct-on-line and star-delta starting line current, starting torque, and star phase voltage; check whether the load can start.

I_Y = I_Δ/3 | T_Y = T_Δ/3 | U_phase,Y = U_line/√3
Electrical & AC

Circuit Breaker Selection

Select a miniature circuit breaker from load current, ambient temperature, and trip curve; check cable ampacity and motor-start inrush.

I_n ≥ K·I_load/temperature factor | I_n ≤ I_z (cable ampacity) | magnetic trip > inrush
Electrical & AC

Contactor / Thermal Overload Relay Selection

Select an AC-3 contactor and thermal-relay setting range from motor rated current, and recommend the trip class from starting time.

I_KM ≥ I_e | I_FR ≈ I_e | trip class 10 / 20 / 30 by starting time
Electrical & AC

CT / Meter Multiplier

Compute the meter multiplier from CT primary/secondary current and PT ratio, then convert secondary current / meter reading to primary current and energy.

K_CT = I₁/I₂ | multiplier = K_CT·K_PT | W₁ = W₂·multiplier
Electrical & AC

Transformer Short-Circuit Current

Estimate secondary symmetrical short-circuit current, short-circuit capacity, and peak current from transformer rating, secondary voltage, and impedance voltage for switchgear breaking checks.

I_sc = S/(√3·U·u_k) | S_sc = S/u_k | i_p ≈ √2·I_sc·(1+e^(−π/(X/R)))
Electrical & AC

Ground Resistance / Electrode

Estimate single-rod ground resistance from soil resistivity and electrode dimensions, then compute parallel resistance and the number of rods needed for the target.

R₁ = ρ/(2πL)·(ln(4L/d) − 1) | R_n = R₁/(n·η)
Electrical & AC

Electric Heating Power / Connection

Compute heating power, phase current, and line current for single-phase / star / delta connection from voltage and per-phase resistance, or scale power with voltage.

P_star = U²/R | P_delta = 3U²/R | P₂ = P₁·(U₂/U₁)²
Electrical & AC

Demand-Factor Load Calculation

Compute active / reactive / apparent load and design current from installed capacity, demand factor, simultaneity factor, and power factor; pre-select transformer capacity.

P_js = K_x·K_Σ·P_e | Q_js = P_js·tanφ | S_js = √(P²+Q²) | I_js = S_js/(√3·U)
Electrical & AC

RCD (Residual Current Device) Selection

Select RCD rated current, residual operating current, and type from load current, protection purpose, and leakage; check cable ampacity and normal leakage.

I_n ≥ K·I_load/temperature factor | I_Δn ≥ 3×normal leakage | personnel protection I_Δn = 30 mAused 1 times
Electrical & AC

SPD (Surge Protective Device) Selection

Select SPD type, Uc, In/Imax, and Up from system voltage, grounding system, installation location, and equipment withstand; check lead length.

U_c ≥ 1.1·U₀ (1.5·U₀ for TT) | U_p,eff = U_p + L·1kV/m | U_p,eff ≤ U_w
Electrical & AC

Conduit / Tray Fill Selection

Compute the required conduit inner diameter from cable outer diameter, count, and bends; recommend a standard size and check actual fill and cable count.

A_cable = n·πd²/4 | A_req = A_cable/fill | D_req = √(4A_req/π)
Electrical & AC

Cable Short-Circuit Thermal Check

Compute the minimum allowable cross-section from short-circuit current, protection clearing time, conductor, and insulation; check cable thermal withstand.

S_min = I_sc·√t / k | I_allow = k·S/√tused 3 times
Electrical & AC

Capacitor Current / Capacitance / Reactor Rate

From reactive compensation, compute capacitor phase current, per-phase capacitance, and rated voltage, with series reactor rate and resonant order.

Q_c = P·(tanφ₁ − tanφ₂) | C = Q_phase/(2πf·U_c²) | h = 1/√p
Electrical & AC

VFD Selection

Select VFD power and current rating from motor power/current, load type, overload requirement, and ambient/altitude derating.

I_VFD ≥ I_e·K_overload/derating | P_VFD ≥ P_e·K/derating
Electrical & AC

UPS Capacity / Battery Backup

Select UPS capacity, battery string voltage, and battery capacity from critical load, power factor, and backup time; back-calculate actual backup time.

S_UPS ≥ P/(cosφ·loading) | C = P·t/(η·DoD·U_bat)
Electrical & AC

Diesel Generator Sizing

Estimate diesel generator capacity from continuous load, largest motor starting method, and power factor; recommend common genset ratings.

S_continuous = P/cosφ×margin | S_start = P_motor×K_start | S_gen = max(S_continuous, S_start)
Electrical & AC

Busbar / Copper Bar Selection

Estimate required busbar cross-section from rated current, material, parallel bars, and ambient temperature; recommend standard copper/aluminum sizes and check current density.

A_req = I/(J·n·temperature factor) | J_Cu ≈ 3 A/mm², J_Al ≈ 2 A/mm²used 10 times
Electrical & AC

Motor Protection Circuit Breaker (MPCB) Selection

Select MPCB frame, thermal-magnetic trip range, and breaking capacity from motor rated current, starting current, and prospective short-circuit current.

I_set ≈ I_e | magnetic trip ≈ 12×I_n | I_cu ≥ I_sc