Required kvar from current to target power factor — the cure for power-factor penalties.

Key points

Reactive Power Compensation: Required kvar from current to target power factor — the cure for power-factor penalties. Formula: Qc = P · (tanφ1 − tanφ2). Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. Compensating to ~0.95 is most economical; too high (>0.98) risks over-compensation oscillation — use automatic bank switching.

Inputs

Qc = P · (tanφ1 − tanφ2)

Calculation model (updates with parameters)

φ1=41°P = 50.0 kWQ = 44.1 kvarS = 66.7 kVAQ'Q' after compensation ≈ 16.4 kvar
Required compensation Qc27.7 kvar
apparent power before compensation66.7 kVA
apparent power after compensation52.6 kVA
current after compensationreduced to 79%

Engineering notes

  • Compensating to ~0.95 is most economical; too high (>0.98) risks over-compensation oscillation — use automatic bank switching.

FAQ

What is Reactive Power Compensation for?
Required kvar from current to target power factor — the cure for power-factor penalties.
What is the formula for Reactive Power Compensation?
Core formula: Qc = P · (tanφ1 − tanφ2). The tool returns results instantly using this formula and the selected parameters.
What engineering notes should I keep in mind when using Reactive Power Compensation?
Compensating to ~0.95 is most economical; too high (>0.98) risks over-compensation oscillation — use automatic bank switching.