Transformer Capacity ↔ Rated Current

Favorite

Primary/secondary rated current from kVA and voltage level — for breaker selection and protection settings.

Key points

Transformer Capacity ↔ Rated Current: Primary/secondary rated current from kVA and voltage level — for breaker selection and protection settings. Formula: I = S / (√3·U) (3-phase) | single-phase I = S / U. Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. On the 400V side, ~144A per 100kVA — use this to size LV busbars / breakers.

Inputs

I = S / (√3·U) (3-phase) | single-phase I = S / U

Calculation model (updates with parameters)

S = 100 kVAPrimaryI = 144.3 Ato loadSecondary
Rated current I144.3 A
rule-of-thumb estimate≈ 375 A
fuse / protection reference217 ~ 289 A

Engineering notes

  • On the 400V side, ~144A per 100kVA — use this to size LV busbars / breakers.

FAQ

What is Transformer Capacity ↔ Rated Current for?
Primary/secondary rated current from kVA and voltage level — for breaker selection and protection settings.
What is the formula for Transformer Capacity ↔ Rated Current?
Core formula: I = S / (√3·U) (3-phase) | single-phase I = S / U. The tool returns results instantly using this formula and the selected parameters.
What engineering notes should I keep in mind when using Transformer Capacity ↔ Rated Current?
On the 400V side, ~144A per 100kVA — use this to size LV busbars / breakers.