Motor Rated Current

Favorite

Rated current from power, efficiency, and power factor, with the "≈2A per kW at 380V 3-phase" rule-of-thumb check.

Key points

Motor Rated Current: Rated current from power, efficiency, and power factor, with the "≈2A per kW at 380V 3-phase" rule-of-thumb check. Formula: I = P / (√3·U·η·cosφ) (three-phase). Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. Set the thermal relay to 1.05–1.1× rated current; size the VFD at 1.1–1.5×.

Inputs

I = P / (√3·U·η·cosφ) (three-phase)

Calculation model (updates with parameters)

three-phase supplyM3~I = 14.9 AP = 7.50 kW
Rated current I14.9 A
rule-of-thumb estimate≈ 15.0 A
input apparent power9.804 kVA
startup current reference89 ~ 104 A

Engineering notes

  • Set the thermal relay to 1.05–1.1× rated current; size the VFD at 1.1–1.5×.

FAQ

What is Motor Rated Current for?
Rated current from power, efficiency, and power factor, with the "≈2A per kW at 380V 3-phase" rule-of-thumb check.
What is the formula for Motor Rated Current?
Core formula: I = P / (√3·U·η·cosφ) (three-phase). The tool returns results instantly using this formula and the selected parameters.
What engineering notes should I keep in mind when using Motor Rated Current?
Set the thermal relay to 1.05–1.1× rated current; size the VFD at 1.1–1.5×.