Select VFD power and current rating from motor power/current, load type, overload requirement, and ambient/altitude derating.

Key points

VFD Selection: Select VFD power and current rating from motor power/current, load type, overload requirement, and ambient/altitude derating. Formula: I_VFD ≥ I_e·K_overload/derating | P_VFD ≥ P_e·K/derating. Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. Selecting a VFD by current is more reliable than by power: motor FLA, overload capability, ambient temperature, and altitude all affect usable current. Constant-torque loads (conveyors, extruders, hoists) need heavy-duty 150%/60 s; fan/pump variable torque may use light-duty, but check starting torque.

Inputs

I_VFD ≥ I_e·K_overload/derating | P_VFD ≥ P_e·K/derating

Calculation model (updates with parameters)

three-phase supplyVFD15 kWM3~MI = 24.75 ADerating 1.00×Cable 30 mSelect by motor FLA and overload capabilityAdd output reactor for long cables
Required VFD current24.75 A
Required VFD power12.38 kW
Temperature / altitude derating1.00 ×
Recommended VFD power rating15 kW
Recommended overload capability150% / 60s
Motor cable length30 m
Voltage / phases380 V,三相

Engineering notes

  • Selecting a VFD by current is more reliable than by power: motor FLA, overload capability, ambient temperature, and altitude all affect usable current.
  • Constant-torque loads (conveyors, extruders, hoists) need heavy-duty 150%/60 s; fan/pump variable torque may use light-duty, but check starting torque.
  • Long motor cables, shielded cables, and parallel motors increase common-mode current and voltage reflection; add output reactors, dv/dt, or sine filters when needed.

FAQ

What is VFD Selection for?
Select VFD power and current rating from motor power/current, load type, overload requirement, and ambient/altitude derating.
What is the formula for VFD Selection?
Core formula: I_VFD ≥ I_e·K_overload/derating | P_VFD ≥ P_e·K/derating. The tool returns results instantly using this formula and the selected parameters.
What engineering notes should I keep in mind when using VFD Selection?
Selecting a VFD by current is more reliable than by power: motor FLA, overload capability, ambient temperature, and altitude all affect usable current. Constant-torque loads (conveyors, extruders, hoists) need heavy-duty 150%/60 s; fan/pump variable torque may use light-duty, but check starting torque. Long motor cables, shielded cables, and parallel motors increase common-mode current and voltage reflection; add output reactors, dv/dt, or sine filters when needed.