Transformer Short-Circuit Current

Favorite

Estimate secondary symmetrical short-circuit current, short-circuit capacity, and peak current from transformer rating, secondary voltage, and impedance voltage for switchgear breaking checks.

Key points

Transformer Short-Circuit Current: Estimate secondary symmetrical short-circuit current, short-circuit capacity, and peak current from transformer rating, secondary voltage, and impedance voltage for switchgear breaking checks. Formula: I_sc = S/(√3·U·u_k) | S_sc = S/u_k | i_p ≈ √2·I_sc·(1+e^(−π/(X/R))). Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. The estimate is a bolted three-phase fault at the transformer secondary, ignoring source impedance, line impedance, and motor contribution; actual values are usually lower. Short-circuit capacity S_sc = S/u_k, and the current multiple is about 1/u_k; lower impedance voltage means higher fault current.

Inputs

I_sc = S/(√3·U·u_k) | S_sc = S/u_k | i_p ≈ √2·I_sc·(1+e^(−π/(X/R)))

Calculation model (updates with parameters)

PrimarySecondary busI_sc = 36.08 kAu_k = 4.0%peak 88.3 kA
Transformer rated current I_n1.443 kA
Short-circuit capacity S_sc25 MVA
Symmetrical short-circuit current I_sc36.08 kA
Short-circuit current multiple25.0 × I_n
Peak short-circuit current i_p88.3 kA
Breaker breaking check未填分断能Force
1 s thermal-equivalent current36.08 kA

Engineering notes

  • The estimate is a bolted three-phase fault at the transformer secondary, ignoring source impedance, line impedance, and motor contribution; actual values are usually lower.
  • Short-circuit capacity S_sc = S/u_k, and the current multiple is about 1/u_k; lower impedance voltage means higher fault current.
  • Switchgear, breakers, and busbars must be checked for peak (dynamic) and I²t (thermal) withstand, not just rated current.

FAQ

What is Transformer Short-Circuit Current for?
Estimate secondary symmetrical short-circuit current, short-circuit capacity, and peak current from transformer rating, secondary voltage, and impedance voltage for switchgear breaking checks.
What is the formula for Transformer Short-Circuit Current?
Core formula: I_sc = S/(√3·U·u_k) | S_sc = S/u_k | i_p ≈ √2·I_sc·(1+e^(−π/(X/R))). The tool returns results instantly using this formula and the selected parameters.
What engineering notes should I keep in mind when using Transformer Short-Circuit Current?
The estimate is a bolted three-phase fault at the transformer secondary, ignoring source impedance, line impedance, and motor contribution; actual values are usually lower. Short-circuit capacity S_sc = S/u_k, and the current multiple is about 1/u_k; lower impedance voltage means higher fault current. Switchgear, breakers, and busbars must be checked for peak (dynamic) and I²t (thermal) withstand, not just rated current.