SPD (Surge Protective Device) Selection

Favorite

Select SPD type, Uc, In/Imax, and Up from system voltage, grounding system, installation location, and equipment withstand; check lead length.

Key points

SPD (Surge Protective Device) Selection: Select SPD type, Uc, In/Imax, and Up from system voltage, grounding system, installation location, and equipment withstand; check lead length. Formula: U_c ≥ 1.1·U₀ (1.5·U₀ for TT) | U_p,eff = U_p + L·1kV/m | U_p,eff ≤ U_w. Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. SPD Uc must exceed the highest sustained system voltage (including tolerance and harmonics), otherwise it ages faster or misoperates. Effective residual voltage = SPD Up + inductive drop in the connecting leads; longer leads raise it, so keep them short, straight, and Kelvin-connected.

Inputs

U_c ≥ 1.1·U₀ (1.5·U₀ for TT) | U_p,eff = U_p + L·1kV/m | U_p,eff ≤ U_w

Calculation model (updates with parameters)

LNSPDType 1Equipment2.00 kVUc 254 V有效残压 2.00 kV
Recommended SPD typeType 1
Minimum continuous voltage U_c≥ 254 V
Recommended nominal discharge current12.5 kA (10/350µs)
SPD voltage protection level U_p1.50 kV
Lead additional residual voltage0.50 kV
Effective residual voltage at equipment U_p,eff2.00 kV
Equipment withstand check通过 ✓
Backup protection按厂家推荐配熔断器 / 断路器

Engineering notes

  • SPD Uc must exceed the highest sustained system voltage (including tolerance and harmonics), otherwise it ages faster or misoperates.
  • Effective residual voltage = SPD Up + inductive drop in the connecting leads; longer leads raise it, so keep them short, straight, and Kelvin-connected.
  • Type 1 / 2 / 3 correspond to main incoming, sub-distribution, and equipment end; energy coordination is required between stages, and backup protection per the manufacturer.

FAQ

What is SPD (Surge Protective Device) Selection for?
Select SPD type, Uc, In/Imax, and Up from system voltage, grounding system, installation location, and equipment withstand; check lead length.
What is the formula for SPD (Surge Protective Device) Selection?
Core formula: U_c ≥ 1.1·U₀ (1.5·U₀ for TT) | U_p,eff = U_p + L·1kV/m | U_p,eff ≤ U_w. The tool returns results instantly using this formula and the selected parameters.
What engineering notes should I keep in mind when using SPD (Surge Protective Device) Selection?
SPD Uc must exceed the highest sustained system voltage (including tolerance and harmonics), otherwise it ages faster or misoperates. Effective residual voltage = SPD Up + inductive drop in the connecting leads; longer leads raise it, so keep them short, straight, and Kelvin-connected. Type 1 / 2 / 3 correspond to main incoming, sub-distribution, and equipment end; energy coordination is required between stages, and backup protection per the manufacturer.