RCD (Residual Current Device) Selection

Favorite

Select RCD rated current, residual operating current, and type from load current, protection purpose, and leakage; check cable ampacity and normal leakage.

Key points

RCD (Residual Current Device) Selection: Select RCD rated current, residual operating current, and type from load current, protection purpose, and leakage; check cable ampacity and normal leakage. Formula: I_n ≥ K·I_load/temperature factor | I_Δn ≥ 3×normal leakage | personnel protection I_Δn = 30 mA. Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. 30 mA RCDs protect people; 300 mA is often used for fire / overall leakage. Upstream and downstream devices should have different residual currents and a discrimination margin. An RCD protects against residual current (leakage) only, not overload or short circuit; socket circuits often use an RCBO (RCD + MCB).

Inputs

I_n ≥ K·I_load/temperature factor | I_Δn ≥ 3×normal leakage | personnel protection I_Δn = 30 mA

Calculation model (updates with parameters)

supplyRCD30 mALoad32 AIn = 50 AA 型I_z = 63 A
Recommended RCD rating I_n50 A
Residual operating current I_Δn30 mA
RCD typeA 型
Normal leakage check通过 ✓
Cable ampacity check通过 ✓
Ambient-temperature derating factor95 %
Protection coordinationRCD + 断路器 / RCBO

Engineering notes

  • 30 mA RCDs protect people; 300 mA is often used for fire / overall leakage. Upstream and downstream devices should have different residual currents and a discrimination margin.
  • An RCD protects against residual current (leakage) only, not overload or short circuit; socket circuits often use an RCBO (RCD + MCB).
  • VFDs, EV charging, and other loads with smooth DC components require Type B; a standard Type A may saturate and fail to trip.

FAQ

What is RCD (Residual Current Device) Selection for?
Select RCD rated current, residual operating current, and type from load current, protection purpose, and leakage; check cable ampacity and normal leakage.
What is the formula for RCD (Residual Current Device) Selection?
Core formula: I_n ≥ K·I_load/temperature factor | I_Δn ≥ 3×normal leakage | personnel protection I_Δn = 30 mA. The tool returns results instantly using this formula and the selected parameters.
What engineering notes should I keep in mind when using RCD (Residual Current Device) Selection?
30 mA RCDs protect people; 300 mA is often used for fire / overall leakage. Upstream and downstream devices should have different residual currents and a discrimination margin. An RCD protects against residual current (leakage) only, not overload or short circuit; socket circuits often use an RCBO (RCD + MCB). VFDs, EV charging, and other loads with smooth DC components require Type B; a standard Type A may saturate and fail to trip.