Motor Protection Circuit Breaker (MPCB) Selection

Favorite

Select MPCB frame, thermal-magnetic trip range, and breaking capacity from motor rated current, starting current, and prospective short-circuit current.

Key points

Motor Protection Circuit Breaker (MPCB) Selection: Select MPCB frame, thermal-magnetic trip range, and breaking capacity from motor rated current, starting current, and prospective short-circuit current. Formula: I_set ≈ I_e | magnetic trip ≈ 12×I_n | I_cu ≥ I_sc. Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. An MPCB combines thermal overload and magnetic short-circuit protection; set the thermal trip to motor FLA and keep the magnetic trip above starting current. Breaking capacity must exceed the prospective short-circuit current at the installation point; if not, add backup fuses or use a higher I_cu model.

Inputs

I_set ≈ I_e | magnetic trip ≈ 12×I_n | I_cu ≥ I_sc

Calculation model (updates with parameters)

supplyMPCB32 AKMM3~MSetting 25 AMagnetic 384 AI_cu 25.0 kA
Recommended MPCB frame32 A
Thermal trip setting I_set25 A
Magnetic trip current (approx.)384 A
Motor starting current150 A
Starting nuisance-trip check通过 ✓
Breaking capacity check通过 ✓
Ambient derating95 %
Protection coordinationMPCB + 接触器 + 热继

Engineering notes

  • An MPCB combines thermal overload and magnetic short-circuit protection; set the thermal trip to motor FLA and keep the magnetic trip above starting current.
  • Breaking capacity must exceed the prospective short-circuit current at the installation point; if not, add backup fuses or use a higher I_cu model.
  • For frequent starts, heavy starts, or high ambient temperature, follow manufacturer derating and coordinate with contactor / thermal-relay characteristics.

FAQ

What is Motor Protection Circuit Breaker (MPCB) Selection for?
Select MPCB frame, thermal-magnetic trip range, and breaking capacity from motor rated current, starting current, and prospective short-circuit current.
What is the formula for Motor Protection Circuit Breaker (MPCB) Selection?
Core formula: I_set ≈ I_e | magnetic trip ≈ 12×I_n | I_cu ≥ I_sc. The tool returns results instantly using this formula and the selected parameters.
What engineering notes should I keep in mind when using Motor Protection Circuit Breaker (MPCB) Selection?
An MPCB combines thermal overload and magnetic short-circuit protection; set the thermal trip to motor FLA and keep the magnetic trip above starting current. Breaking capacity must exceed the prospective short-circuit current at the installation point; if not, add backup fuses or use a higher I_cu model. For frequent starts, heavy starts, or high ambient temperature, follow manufacturer derating and coordinate with contactor / thermal-relay characteristics.