Demand-Factor Load Calculation

Favorite

Compute active / reactive / apparent load and design current from installed capacity, demand factor, simultaneity factor, and power factor; pre-select transformer capacity.

Key points

Demand-Factor Load Calculation: Compute active / reactive / apparent load and design current from installed capacity, demand factor, simultaneity factor, and power factor; pre-select transformer capacity. Formula: P_js = K_x·K_Σ·P_e | Q_js = P_js·tanφ | S_js = √(P²+Q²) | I_js = S_js/(√3·U). Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. The demand-factor method suits preliminary design / estimates; obtain K_x and K_Σ from design manuals or local supply guides for each load type. Design current is used for the incoming breaker, busbars, and cables; transformer rating also considers loading, future expansion, starting current, and reactive compensation.

Inputs

P_js = K_x·K_Σ·P_e | Q_js = P_js·tanφ | S_js = √(P²+Q²) | I_js = S_js/(√3·U)

Calculation model (updates with parameters)

Equipment容量100 kWCalculate有功70 kWCalculate无功43.38 kvarCalculate视在82.35 kVACalculatecurrent 125.1 A;变压器按 0.8 load率初选
Total installed capacity P_e100 kW
Calculated active power P_js70 kW
Calculated reactive power Q_js43.38 kvar
Calculated apparent power S_js82.35 kVA
Calculated current I_js125.1 A
Power factor cosφ0.85
Transformer for 0.8 loading102.9 kVA
Recommended transformer rating125 kVA
⚠ Power factor低于 0.9:可能产生Force调电费,建议同步做无功补偿(见「Reactive Power Compensation」工具)。

Engineering notes

  • The demand-factor method suits preliminary design / estimates; obtain K_x and K_Σ from design manuals or local supply guides for each load type.
  • Design current is used for the incoming breaker, busbars, and cables; transformer rating also considers loading, future expansion, starting current, and reactive compensation.
  • Calculate P and Q for each load group and sum them; do not add apparent powers directly. Low power factor means large reactive share, occupying transformer and line capacity.

FAQ

What is Demand-Factor Load Calculation for?
Compute active / reactive / apparent load and design current from installed capacity, demand factor, simultaneity factor, and power factor; pre-select transformer capacity.
What is the formula for Demand-Factor Load Calculation?
Core formula: P_js = K_x·K_Σ·P_e | Q_js = P_js·tanφ | S_js = √(P²+Q²) | I_js = S_js/(√3·U). The tool returns results instantly using this formula and the selected parameters.
What engineering notes should I keep in mind when using Demand-Factor Load Calculation?
The demand-factor method suits preliminary design / estimates; obtain K_x and K_Σ from design manuals or local supply guides for each load type. Design current is used for the incoming breaker, busbars, and cables; transformer rating also considers loading, future expansion, starting current, and reactive compensation. Calculate P and Q for each load group and sum them; do not add apparent powers directly. Low power factor means large reactive share, occupying transformer an…