Ground Resistance / Electrode

Favorite

Estimate single-rod ground resistance from soil resistivity and electrode dimensions, then compute parallel resistance and the number of rods needed for the target.

Key points

Ground Resistance / Electrode: Estimate single-rod ground resistance from soil resistivity and electrode dimensions, then compute parallel resistance and the number of rods needed for the target. Formula: R₁ = ρ/(2πL)·(ln(4L/d) − 1) | R_n = R₁/(n·η). Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. The vertical-rod formula assumes uniform soil and a single driven round rod; layered soil, seasonal variation, and nearby electrodes can change results significantly. Parallel rods are not simply divided by n; the utilization factor η drops as rod count rises and spacing shrinks, commonly 0.6–0.9.

Inputs

R₁ = ρ/(2πL)·(ln(4L/d) − 1) | R_n = R₁/(n·η)

Calculation model (updates with parameters)

3 mGround levelρ = 100 Ω·mR₁ = 29.82 ΩR_n = 29.82 Ω需 10 根
Single vertical rod resistance R₁29.82 Ω
1 根Shunt接地Resistance R_n29.82 Ω
Rods required for target10 根
Target ground resistance4 Ω
Target met?未达标 ✗
Average resistance per rod29.82 Ω
Soil resistivity100 Ω·m
⚠ 当前 1 根Shunt接地Resistance 29.82 Ω 仍高于target 4 Ω:增加到≈ 10 根,或采用接地网 / 降阻剂。

Engineering notes

  • The vertical-rod formula assumes uniform soil and a single driven round rod; layered soil, seasonal variation, and nearby electrodes can change results significantly.
  • Parallel rods are not simply divided by n; the utilization factor η drops as rod count rises and spacing shrinks, commonly 0.6–0.9.
  • Protective, lightning, and electronic grounding have different requirements; measure with a ground resistance tester after installation, not just calculations.

FAQ

What is Ground Resistance / Electrode for?
Estimate single-rod ground resistance from soil resistivity and electrode dimensions, then compute parallel resistance and the number of rods needed for the target.
What is the formula for Ground Resistance / Electrode?
Core formula: R₁ = ρ/(2πL)·(ln(4L/d) − 1) | R_n = R₁/(n·η). The tool returns results instantly using this formula and the selected parameters.
What engineering notes should I keep in mind when using Ground Resistance / Electrode?
The vertical-rod formula assumes uniform soil and a single driven round rod; layered soil, seasonal variation, and nearby electrodes can change results significantly. Parallel rods are not simply divided by n; the utilization factor η drops as rod count rises and spacing shrinks, commonly 0.6–0.9. Protective, lightning, and electronic grounding have different requirements; measure with a ground resistance tester after installation, not just calculations.