Contactor / Thermal Overload Relay Selection

Favorite

Select an AC-3 contactor and thermal-relay setting range from motor rated current, and recommend the trip class from starting time.

Key points

Contactor / Thermal Overload Relay Selection: Select an AC-3 contactor and thermal-relay setting range from motor rated current, and recommend the trip class from starting time. Formula: I_KM ≥ I_e | I_FR ≈ I_e | trip class 10 / 20 / 30 by starting time. Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. Select contactor current for AC-3 duty; for frequent jogging / heavy starting, upsize per the manufacturer derating curve. Do not rely only on motor nameplate current. Set the thermal relay to the motor nameplate FLA / rated current, not the contactor rating; use class 20 / 30 for long starts.

Inputs

I_KM ≥ I_e | I_FR ≈ I_e | trip class 10 / 20 / 30 by starting time

Calculation model (updates with parameters)

supplyQFKM32 AFR17.0~25.0 AM3~MSetting 25 AThermal relay 10 级
Motor rated current I_e25 A
Recommended AC-3 contactor rating32 A
Contactor current margin1.28 ×
Thermal relay setting I_set25 A
Recommended thermal relay range17.0 ~ 25.0 A
Recommended trip class10 级
Starting current I_st150 A
Starts-per-hour check正常 ✓

Engineering notes

  • Select contactor current for AC-3 duty; for frequent jogging / heavy starting, upsize per the manufacturer derating curve. Do not rely only on motor nameplate current.
  • Set the thermal relay to the motor nameplate FLA / rated current, not the contactor rating; use class 20 / 30 for long starts.
  • The thermal relay protects against motor overload, not short circuit; the breaker / fuse provides short-circuit protection and the two must coordinate.

FAQ

What is Contactor / Thermal Overload Relay Selection for?
Select an AC-3 contactor and thermal-relay setting range from motor rated current, and recommend the trip class from starting time.
What is the formula for Contactor / Thermal Overload Relay Selection?
Core formula: I_KM ≥ I_e | I_FR ≈ I_e | trip class 10 / 20 / 30 by starting time. The tool returns results instantly using this formula and the selected parameters.
What engineering notes should I keep in mind when using Contactor / Thermal Overload Relay Selection?
Select contactor current for AC-3 duty; for frequent jogging / heavy starting, upsize per the manufacturer derating curve. Do not rely only on motor nameplate current. Set the thermal relay to the motor nameplate FLA / rated current, not the contactor rating; use class 20 / 30 for long starts. The thermal relay protects against motor overload, not short circuit; the breaker / fuse provides short-circuit protection and the two must coordinate.