Contactor / Thermal Overload Relay Selection
Select an AC-3 contactor and thermal-relay setting range from motor rated current, and recommend the trip class from starting time.
Key points
Contactor / Thermal Overload Relay Selection: Select an AC-3 contactor and thermal-relay setting range from motor rated current, and recommend the trip class from starting time. Formula: I_KM ≥ I_e | I_FR ≈ I_e | trip class 10 / 20 / 30 by starting time. Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. Select contactor current for AC-3 duty; for frequent jogging / heavy starting, upsize per the manufacturer derating curve. Do not rely only on motor nameplate current. Set the thermal relay to the motor nameplate FLA / rated current, not the contactor rating; use class 20 / 30 for long starts.
Inputs
I_KM ≥ I_e | I_FR ≈ I_e | trip class 10 / 20 / 30 by starting timeCalculation model (updates with parameters)
| Motor rated current I_e | 25 A | 热继电器整定基准 |
| Recommended AC-3 contactor rating | 32 A | 所needs ≥ 26.32 A(含Temperature降额) |
| Contactor current margin | 1.28 × | recommend ≥1.1× |
| Thermal relay setting I_set | 25 A | 按motor铭牌 FLA 整定,不按接触器额定Value |
| Recommended thermal relay range | 17.0 ~ 25.0 A | 选择包含 I_set 的可调范围 |
| Recommended trip class | 10 级 | Starting time 8.0 s:10 级 ≤10s,20 级 ≤20s,30 级 >20s |
| Starting current I_st | 150 A | I_e × 启动×数 |
| Starts-per-hour check | 正常 ✓ | 6 次/h,建议 ≤30 次/h |
Engineering notes
- Select contactor current for AC-3 duty; for frequent jogging / heavy starting, upsize per the manufacturer derating curve. Do not rely only on motor nameplate current.
- Set the thermal relay to the motor nameplate FLA / rated current, not the contactor rating; use class 20 / 30 for long starts.
- The thermal relay protects against motor overload, not short circuit; the breaker / fuse provides short-circuit protection and the two must coordinate.
FAQ
- What is Contactor / Thermal Overload Relay Selection for?
- Select an AC-3 contactor and thermal-relay setting range from motor rated current, and recommend the trip class from starting time.
- What is the formula for Contactor / Thermal Overload Relay Selection?
- Core formula: I_KM ≥ I_e | I_FR ≈ I_e | trip class 10 / 20 / 30 by starting time. The tool returns results instantly using this formula and the selected parameters.
- What engineering notes should I keep in mind when using Contactor / Thermal Overload Relay Selection?
- Select contactor current for AC-3 duty; for frequent jogging / heavy starting, upsize per the manufacturer derating curve. Do not rely only on motor nameplate current. Set the thermal relay to the motor nameplate FLA / rated current, not the contactor rating; use class 20 / 30 for long starts. The thermal relay protects against motor overload, not short circuit; the breaker / fuse provides short-circuit protection and the two must coordinate.