Cable Short-Circuit Thermal Check

Favorite

Compute the minimum allowable cross-section from short-circuit current, protection clearing time, conductor, and insulation; check cable thermal withstand.

Key points

Cable Short-Circuit Thermal Check: Compute the minimum allowable cross-section from short-circuit current, protection clearing time, conductor, and insulation; check cable thermal withstand. Formula: S_min = I_sc·√t / k | I_allow = k·S/√t. Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. Thermal withstand ensures conductor temperature during a fault stays within insulation limits; k depends on conductor and insulation, and this tool uses common values. Use the actual clearing time (including breaker opening and protection delay), not just the instantaneous setting.

Inputs

S_min = I_sc·√t / k | I_allow = k·S/√t

Calculation model (updates with parameters)

S = 70 mm²Actual cross-sectionS_min55.28 mm²S_min = I_sc·√t / k;Longer fault time and higher current require a larger section
Thermal coefficient k143
Minimum thermal cross-section S_min55.28 mm²
Actual cable cross-section S70 mm²
Recommended standard cross-section70 mm²
Allowable short-circuit current for this section31.65 kA
Thermal withstand check通过 ✓
Short-circuit thermal effect I²t62.5 kA²·s

Engineering notes

  • Thermal withstand ensures conductor temperature during a fault stays within insulation limits; k depends on conductor and insulation, and this tool uses common values.
  • Use the actual clearing time (including breaker opening and protection delay), not just the instantaneous setting.
  • Use the maximum short-circuit capacity at the installation point; for parallel cables, check total section and current sharing, not a single cable.

FAQ

What is Cable Short-Circuit Thermal Check for?
Compute the minimum allowable cross-section from short-circuit current, protection clearing time, conductor, and insulation; check cable thermal withstand.
What is the formula for Cable Short-Circuit Thermal Check?
Core formula: S_min = I_sc·√t / k | I_allow = k·S/√t. The tool returns results instantly using this formula and the selected parameters.
What engineering notes should I keep in mind when using Cable Short-Circuit Thermal Check?
Thermal withstand ensures conductor temperature during a fault stays within insulation limits; k depends on conductor and insulation, and this tool uses common values. Use the actual clearing time (including breaker opening and protection delay), not just the instantaneous setting. Use the maximum short-circuit capacity at the installation point; for parallel cables, check total section and current sharing, not a single cable.