Circuit Breaker Selection

Favorite

Select a miniature circuit breaker from load current, ambient temperature, and trip curve; check cable ampacity and motor-start inrush.

Key points

Circuit Breaker Selection: Select a miniature circuit breaker from load current, ambient temperature, and trip curve; check cable ampacity and motor-start inrush. Formula: I_n ≥ K·I_load/temperature factor | I_n ≤ I_z (cable ampacity) | magnetic trip > inrush. Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. Breaker In must be both ≥ design load current (with margin) and ≤ cable ampacity Iz; both conditions are mandatory. B / C / D curves set the magnetic-trip threshold. Motor inrush can reach 6–8×In; if C still trips, use D or a larger frame.

Inputs

I_n ≥ K·I_load/temperature factor | I_n ≤ I_z (cable ampacity) | magnetic trip > inrush

Calculation model (updates with parameters)

supplyQFCLoad32 AIn = 50 AI_z = 63 A瞬时 5~10×In
Design load current I_load32 A
Ambient-temperature derating factor95 %
Required minimum current rating42.11 A
Recommended breaker In50 A
Actual current margin1.56 ×
Trip curve / magnetic rangeC 曲线(5~10×In)
Cable ampacity check通过 ✓
Motor starting check不适用

Engineering notes

  • Breaker In must be both ≥ design load current (with margin) and ≤ cable ampacity Iz; both conditions are mandatory.
  • B / C / D curves set the magnetic-trip threshold. Motor inrush can reach 6–8×In; if C still trips, use D or a larger frame.
  • Ambient temperature, side-by-side mounting, harmonics, and altitude reduce actual ampacity; critical circuits also need breaking-capacity and selectivity checks.

FAQ

What is Circuit Breaker Selection for?
Select a miniature circuit breaker from load current, ambient temperature, and trip curve; check cable ampacity and motor-start inrush.
What is the formula for Circuit Breaker Selection?
Core formula: I_n ≥ K·I_load/temperature factor | I_n ≤ I_z (cable ampacity) | magnetic trip > inrush. The tool returns results instantly using this formula and the selected parameters.
What engineering notes should I keep in mind when using Circuit Breaker Selection?
Breaker In must be both ≥ design load current (with margin) and ≤ cable ampacity Iz; both conditions are mandatory. B / C / D curves set the magnetic-trip threshold. Motor inrush can reach 6–8×In; if C still trips, use D or a larger frame. Ambient temperature, side-by-side mounting, harmonics, and altitude reduce actual ampacity; critical circuits also need breaking-capacity and selectivity checks.