Three-phase / Single-phase Power (Supply Standards)

Favorite

Calculate apparent, active and reactive power, line and phase current for single-phase or balanced three-phase loads using national/regional supply standards (China 220/380 V, Europe 230/400 V, US 120/277/480 V, Japan 100/200 V…) or a custom voltage — and work back from power to current.

Key points

The three-phase / single-phase power calculator uses the nominal voltage of the selected national supply standard (China 220/380 V, Europe 230/400 V, US 120/240/277/480 V, Japan 100/200 V, or a custom voltage). For balanced three-phase loads S = √3·U_L·I_L, for single-phase S = U·I; active power P = S·cosφ and reactive power Q = S·sinφ. Given active power it back-calculates current: three-phase I_L = P/(√3·U_L·cosφ), single-phase I = P/(U·cosφ). In a Y connection the phase current equals the line current, while in Δ the phase current is I_L/√3.

Inputs

Three-phase S = √3·U_L·I_L | single-phase S = U·I | P = S·cosφ | Q = S·sinφ

Calculation model (updates with parameters)

φ=32°P = 5.595 kWQ = 3.467 kvarS = 6.582 kVA3~ source380 VL1L2L3load10 AU_L = 380 V · I_L = 10 A · cosφ = 0.85P = 5.595 kW · Q = 3.467 kvar · S = 6.582 kVA
Supply standard / phase systemChina 220 / 380 V · 50 Hz
Line / phase voltage380 V / 220 V
Apparent power S6.582 kVA
Active power P5.595 kW
Reactive power Q3.467 kvar
Power factor0.85
Line current I_L10 A
Phase current (Y / Δ)10 A / 5.774 A
Active power per phase1.865 kW
⚠ Power factor <0.9: the reactive share is large — reactive compensation is recommended.

Engineering notes

  • For a balanced three-phase load, S = √3·U_L·I_L is independent of the Y / Δ connection, but the phase current is not: Y gives phase current = line current, Δ gives phase current = line current/√3.
  • These are nominal voltages (China 220/380 V, Europe 230/400 V, …); real grids allow about ±10%. Choose “Custom voltage” to calculate with a measured value.
  • For the same power the three-phase current is about 1/3 of the single-phase current; for single-phase loads above 32 A prefer a three-phase supply to save on conductors and breakers.
  • A power factor below 0.9 may incur power-factor penalty charges; estimate the compensation with the “Power factor correction capacitor” tool.

FAQ

What is Three-phase / Single-phase Power (Supply Standards) for?
Calculate apparent, active and reactive power, line and phase current for single-phase or balanced three-phase loads using national/regional supply standards (China 220/380 V, Europe 230/400 V, US 120/277/480 V, Japan 100/200 V…) or a custom voltage — and work back from power to current.
What is the formula for Three-phase / Single-phase Power (Supply Standards)?
Core formula: Three-phase S = √3·U_L·I_L | single-phase S = U·I | P = S·cosφ | Q = S·sinφ. The tool returns results instantly using this formula and the selected parameters.
What engineering notes should I keep in mind when using Three-phase / Single-phase Power (Supply Standards)?
For a balanced three-phase load, S = √3·U_L·I_L is independent of the Y / Δ connection, but the phase current is not: Y gives phase current = line current, Δ gives phase current = line current/√3. These are nominal voltages (China 220/380 V, Europe 230/400 V, …); real grids allow about ±10%. Choose “Custom voltage” to calculate with a measured value. For the same power the three-phase current is about 1/3 of the single-phase current; for single-phase loads above 32 A prefer…