Choose a fuse rating from continuous load current, ambient temperature, and surge I²t; check derating, melting integral, and voltage rating to avoid nuisance blowing.

Key points

Fuse Selection: Choose a fuse rating from continuous load current, ambient temperature, and surge I²t; check derating, melting integral, and voltage rating to avoid nuisance blowing. Formula: In ≥ Iload/(derating × temperature factor) | I²t_fuse ≥ 2 × I_inrush²·t_inrush. Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. A fuse rating is not the operating current; apply continuous-current derating (often 75% for UL) and the ambient-temperature factor. Check capacitive-load and motor-start surges by I²t: fuse I²t should exceed surge I²t with at least 2× margin, otherwise it blows at power-up.

Inputs

In ≥ Iload/(derating × temperature factor) | I²t_fuse ≥ 2 × I_inrush²·t_inrush

Calculation model (updates with parameters)

InputF13.15 Aload2 A24 V 系统40 °C Surroundings
Ambient-temperature derating factor95 %
Combined derating factor71 %
Required minimum current rating2.807 A
Recommended fuse rating In3.15 A
Actual load ratio63 %
Surge I²t (actual)0.500 A²·s
Required fuse I²t (with margin)1.000 A²·s
Selected I²t check未填额定Value
Voltage rating check通过 ✓

Engineering notes

  • A fuse rating is not the operating current; apply continuous-current derating (often 75% for UL) and the ambient-temperature factor.
  • Check capacitive-load and motor-start surges by I²t: fuse I²t should exceed surge I²t with at least 2× margin, otherwise it blows at power-up.
  • Use DC-rated fuses for high-voltage DC; breaking capacity must exceed the prospective short-circuit current, with TVS / MOV coordination if needed.

FAQ

What is Fuse Selection for?
Choose a fuse rating from continuous load current, ambient temperature, and surge I²t; check derating, melting integral, and voltage rating to avoid nuisance blowing.
What is the formula for Fuse Selection?
Core formula: In ≥ Iload/(derating × temperature factor) | I²t_fuse ≥ 2 × I_inrush²·t_inrush. The tool returns results instantly using this formula and the selected parameters.
What engineering notes should I keep in mind when using Fuse Selection?
A fuse rating is not the operating current; apply continuous-current derating (often 75% for UL) and the ambient-temperature factor. Check capacitive-load and motor-start surges by I²t: fuse I²t should exceed surge I²t with at least 2× margin, otherwise it blows at power-up. Use DC-rated fuses for high-voltage DC; breaking capacity must exceed the prospective short-circuit current, with TVS / MOV coordination if needed.