Thermocouple mV ↔ Temperature (Cold-Junction Compensated)

Favorite

Convert thermocouple EMF to temperature for K/J/T/E types with cold-junction compensation — forgetting this step is why a meter reading can be tens of degrees off.

Key points

Thermocouple mV ↔ Temperature (Cold-Junction Compensated): Convert thermocouple EMF to temperature for K/J/T/E types with cold-junction compensation — forgetting this step is why a meter reading can be tens of degrees off. Formula: E(T_hot) = E_meas + E(T_cold), then look up the table. Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. Uses ITS-90 reference points every 100°C with interpolation; error stays under 1°C from 0°C to the upper limit. Use the full tables for precision metrology. A common alternative is to measure the terminal temperature with a PT100/DS18B20 and use this tool — far more accurate than assuming 25°C.

Inputs

E(T_hot) = E_meas + E(T_cold), then look up the table

Calculation model (updates with parameters)

热端 324 ℃mV冷端补偿T_cold12.209 mVE_total = E_meas + E(T_cold)
Hot-junction temperature324.5 ℃
Compensated EMF E(T)13.2330 mV
Cold-junction compensation1.0240 mV
Type / rangeK 型 0~1000 ℃

Engineering notes

  • Uses ITS-90 reference points every 100°C with interpolation; error stays under 1°C from 0°C to the upper limit. Use the full tables for precision metrology.
  • A common alternative is to measure the terminal temperature with a PT100/DS18B20 and use this tool — far more accurate than assuming 25°C.
  • Reversed polarity reads strongly negative; compensation cable must match the thermocouple type and polarity at the terminals.

FAQ

What is Thermocouple mV ↔ Temperature (Cold-Junction Compensated) for?
Convert thermocouple EMF to temperature for K/J/T/E types with cold-junction compensation — forgetting this step is why a meter reading can be tens of degrees off.
What is the formula for Thermocouple mV ↔ Temperature (Cold-Junction Compensated)?
Core formula: E(T_hot) = E_meas + E(T_cold), then look up the table. The tool returns results instantly using this formula and the selected parameters.
What engineering notes should I keep in mind when using Thermocouple mV ↔ Temperature (Cold-Junction Compensated)?
Uses ITS-90 reference points every 100°C with interpolation; error stays under 1°C from 0°C to the upper limit. Use the full tables for precision metrology. A common alternative is to measure the terminal temperature with a PT100/DS18B20 and use this tool — far more accurate than assuming 25°C. Reversed polarity reads strongly negative; compensation cable must match the thermocouple type and polarity at the terminals.