PLC Analog Scaling (27648 / 32767 / 4000)

Favorite

Two-way conversion between PLC analog codes and engineering values for Siemens 27648, generic 32767 and Mitsubishi/Omron 4000 full scales, with wire-break and over-range detection.

Key points

PLC Analog Scaling (27648 / 32767 / 4000): Two-way conversion between PLC analog codes and engineering values for Siemens 27648, generic 32767 and Mitsubishi/Omron 4000 full scales, with wire-break and over-range detection. Formula: Value = LRV + (code/full-scale code × signal span − signal low)/(signal span) × (URV − LRV). Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. S7 unipolar modules map 0–20mA (0–10V) onto 0–27648, so 4mA is about 5530 counts, not zero. Scale with the lower-limit and full-scale counts as your two points rather than mapping 0/27648 to 4/20mA.

Inputs

Value = LRV + (code/full-scale code × signal span − signal low)/(signal span) × (URV − LRV)

Calculation model (updates with parameters)

069121382420736276480 – 27648 (S7 unipolar)Code 13824 → 37.5 °C4mA ≈ 5530 · 12mA ≈ 13824 · 20mA = 27648
Engineering value37.500 °C
Signal value10.000 mA
Percent of signal span37.50 %
Loop statusWithin range
Lower / full-scale code5530 / 27648

Engineering notes

  • S7 unipolar modules map 0–20mA (0–10V) onto 0–27648, so 4mA is about 5530 counts, not zero.
  • Scale with the lower-limit and full-scale counts as your two points rather than mapping 0/27648 to 4/20mA.

FAQ

What is PLC Analog Scaling (27648 / 32767 / 4000) for?
Two-way conversion between PLC analog codes and engineering values for Siemens 27648, generic 32767 and Mitsubishi/Omron 4000 full scales, with wire-break and over-range detection.
What is the formula for PLC Analog Scaling (27648 / 32767 / 4000)?
Core formula: Value = LRV + (code/full-scale code × signal span − signal low)/(signal span) × (URV − LRV). The tool returns results instantly using this formula and the selected parameters.
What engineering notes should I keep in mind when using PLC Analog Scaling (27648 / 32767 / 4000)?
S7 unipolar modules map 0–20mA (0–10V) onto 0–27648, so 4mA is about 5530 counts, not zero. Scale with the lower-limit and full-scale counts as your two points rather than mapping 0/27648 to 4/20mA.